Technical Manual
–
Central Operation Unit Smart
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Phone: +49-2263-
880 • Fax: +49-2263-4588 • [email protected] • www.mdt.de
115
115
2 Byte shift of basis comfort setpoint
In the case of the 2-byte shift of basic comfort setpoint, the central operating unit sends a new basic
comfort setpoint to the controller. It evaluates the object "state basis comfort setpoint" and sends
the new se/- the set step width to the controller.
The range of the setpoint shift can be adjusted via the upper and lower limits.
The following table shows the available communication objects:
Number
Name
Length
Usage
100
Push buttons 1/2
–
basis comfort setpoint
2 Byte
Sends the new Basis Comfort Setpoint
101
Push buttons 1/2
–
State actual temperature
2 Byte
Receiving an external temperature for the
display of the current temperature - is only
displayed if the parameter "Use internal
temperature value" is set to "not active"
102
Push buttons 1/2
–
State current setpoint
temperature
2 Byte
Receiving the current setpoint temperature of
the temperature controller; to display the
status
103
Push buttons 1/2
–
State basis comfort
setpoint
2 Byte
Receives the current setpoint shift; has to be
connected to the basic comfort setpoint value
of the controller so that the basic comfort
setpoint can be correctly displaced even when
changing to a different operating mode
Table 115: Communication objects - 2 Byte shift of comfort setpoint value
Presentation:
Two-button function
The temperature shift is represented by the temperature symbol. The display is fixed to the symbol 9.
In addition, the actual value and the desired value can be labeled as desired:
Figure 66: Presentation - Temperature shift