Technical Manual
–
Central Operation Unit Smart
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Phone: +49-2263-
880 • Fax: +49-2263-4588 • [email protected] • www.mdt.de
88
88
Subfunction: Toggle
Single-button function
With the single button function "Switch" - Subfunction: Toggle, the key sends the respective inverted
value with respect to the last received status value.For this purpose, the status object "value for
toggle" has to be connected with the status of the actuator to be switched. If an "on" signal has been
received as last value, the push button sends an "off" command at the next keystroke and vice versa.
The following figure shows the available settings:
Figure 47: Settings: Single-
button function „Switch“
- Toggle
The following table shows the available communication objects:
Number
Name
Length
Usage
100
Direct button 1
–
switch
1 Bit
Switch function of the button
101
Direct button 1
–
Value for toggle
1 Bit
Status to refresh the display/symbol on the
button; has to be connected to the status of
the actuator to be switched so that the correct
(inverted) value is always transmitted
Table 82: Communication objects: Single-
button function „Switch“ –
Toggle
Subfunction: Send status
Single-button function
With the single button function "Switch" - Subfunction: Send status, fixed values for an activated key
(rising edge) and a released key (falling edge) can be sent. With this function, scanning applications
can be realized.
The following figure shows the available settings:
Figure 48: Settings: Single-
button function „Switch“
- Send Status
The following table shows the available communication objects:
Number
Name
Length
Usage
100
Direct button 1
–
send
status
1 Bit
Switch function of the button
103
Direct button 1
–
State for display
1 Bit
State to refresh the display/symbol on the
button; has to be connected to the state of the
actuator to be switched
Table 83: Communication objects: Single-
button function „Switch“
- Send Status