Technical Manual
–
Central Operation Unit Smart
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Phone: +49-2263-
880 • Fax: +49-2263-4588 • [email protected] • www.mdt.de
132
132
Presentation
The display of the function "Send values" depends on the selected data point type. Depending on the
selected data point type, 1-4 different symbols and their color can be selected.
The following table provides an overview of the settings for the various data point types:
Datapoint type
Adjustable symbols
Comment
2 Bit Switch control, DPT 2.001
4 symbols can be set: 1 symbol
for each possible state
1 Byte Percent, DPT 5.001
3 symbols can be set for the
ranges 0, 1-229 and 230-255.
Therefore, the button evaluates
the information of the "Status
for display" object
Special presentation possible!
Additionally it is possible to
display the status value below
the symbol.
1 Byte Decimal fator, DPT 5.005 3 symbols can be set for the
ranges 0%, 1% - 90% and >90%.
Therefore the button evaluates
the information of the "Status
for display" object
Special presentation possible!
Additionally it is possible to
display the status value below
the symbol.
1 Byte Scene Number, DPT
17.001
1 fixed symbol can be set
2 Byte Colour temperature,
DPT 7.600
1 or 2 symbols can be set: 1 for
each switching value
2 Byte Temperature, DPT 9.001
1 fixed symbol can be set
Special presentation possible!
2 Byte Brightness, DPT 9.004
1 fixed symbol can be set
Table 125: Presentation - Send values
Special presentation:
For certain data point types, a special presentation (see table above) is possible. In this presentation,
the status is shown on a larger scale on the display.
The following presentations are possible:
ETS-Text
Dynamic range
[Default value]
Comment
Special display
(DPT 5.001, DPT 5.005)
▪
value as text (0-100%)
▪
value as text (0-255)
▪
link symbol with
switching value
With the settings "value as
text" the text is displayed large
on the display.
Special display
(DPT 9.001)
▪
value as “°C”
▪
value as symbol without
unit
▪
value as “K”
▪
link symbol with
switching value
With the settings "value as
symbol" the text is displayed
large on the display.
Table 126: Presentation - Special symbols