Technical Manual
–
Central Operation Unit Smart
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Phone: +49-2263-
880 • Fax: +49-2263-4588 • [email protected] • www.mdt.de
114
114
2 Byte temperature shift
With the 2-byte temperature shift, the central operating unit sends a 2-byte temperature value
which is added or subtracted from the set basic comfort value.
The central operating unit sends the shift by the set step width at each keystroke.
In order for the display and the current reference value to be synchronous, the limits of the setpoint
shift must be specified in the central operating unit and have to be set to the same values as in the
controller.
The following table shows the available communication objects:
Number
Name
Length
Usage
100
Direct buttons 1/2
–
Setpoint shift
1 Bit
Sends the Setpoint shift
101
Direct buttons 1/2
–
State actual temperature
2 Byte
Receiving an external temperature for the
display of the current temperature - is only
displayed if the parameter "Use internal
temperature value" is set to "not active"
102
Direct buttons 1/2
–
State current setpoint
temperature
2 Byte
Receiving the current setpoint temperature of
the temperature controller; to display the
status
103
Direct buttons 1/2
–
State setpoint shift
1 Byte
Receives the current setpoint shift; has to be
connected to all 1 byte objects which send the
setpoint shift to the controller in order to
correctly evaluate the current status of the
setpoint shift
Table 114: Communication objects - Temperature shift via 2 byte