© 2015 Sensata Technologies
Operation
40
Function
Settings/Ranges
Inverter/Remote
Settings
(DIP Switch 1)
UP
1
= Use Inverter Settings
DOWN = Use Remote Settings
Ignition Control
(DIP Switch 2)
UP
1
= Ignition Control Disabled
DOWN = Ignition Control Enabled
Ground Control
(DIP Switch 3)
UP
1
= Ground Control Disabled
DOWN = Ground Control Enabled
Search Mode
2
(DIP Switch 4)
UP
1
= (Search off) Full AC Output
DOWN = Search Mode Activated (5W)
Charge Rate
2
(DIP Switch 5)
UP
1
= 100% (50A)
DOWN = 30% (15A)
Battery Type
2
(DIP Switches 6 & 7)
Both UP
1
= Flooded
(Absorb = 14.6 VDC, Float = 13.4 VDC)
Other DIP settings: AGM1, AGM2, and GEL
Absorb Time
2
(DIP Switches 8 & 9)
Both UP
1
= 60 Minutes
Other DIP settings: 90, 120, & 150 minutes
EQ Enable
2
(DIP Switch 10)
UP
1
= EQ Charge Disabled
DOWN = Start EQ Charge
LowBatCutOut
2
10.0 VDC
1
VAC Dropout
2
80 VAC
1
Note
1
: Inverter and DIP switch default settings.
Note
2
: Optional ME-RC and ME-ARC remote controls provide additional
settings for these functions.
Table 4-3, MMSA Inverter/DIP Switch Settings
4.5 Summary of Inverter/DIP Switch Settings
Your MMSA1012 inverter uses default settings (established by DIP
switch positions) that are adequate for most installations. However,
if you determine that some of your operating parameters need to
be changed, Sensata offers several remotes (Section 2.6) that allow
you to customize the programming parameters of the inverter/
charger.