GRAFIK Eye
®
QS Control Unit Installation and Operation Guide 22
Setting Save Mode
The Save Mode of the GRAFIK Eye
®
QS control unit can be adjusted to turn quick
scene programming on and off, or to disable the use of zone and/or scene buttons
for specific applications.
Save Mode Settings
Save by OK (default): Quick scene programming mode; zone
adjustments are temporary until the “OK” button is pressed to
confirm the selection.
Save always: Automatically save changes made to lighting
levels or fade time to Off (Master button changes are
temporary).
Save never: Do not save any temporary changes to lighting
levels or fade time.
Four scenes (typically used for rented spaces): Zone raise/
lower buttons are disabled. Master raise/lower buttons,
wallstations, and IR receiver are still enabled for adjustment
of light level, but these changes are not saved.
Button disable (typically used in a public space): Only the
Timeclock button, IR receiver, and wallstations can be used
to make temporary changes.
Changing the Save Mode
1. Enter programming mode.
2. Use the Master buttons to highlight “Save mode” and press
the “OK” button to accept.
3. Use the Master buttons to highlight the desired save mode.
The save modes are listed and explained below.
4. Press the “OK” button to accept. The info screen will confirm
that your save mode has been saved.
5. Exit programming mode.
Main menu
Scene setup
Save mode
Save mode
Save always
OK
Master
buttons
“OK”
button
Saved
Quick Scene Programming:
“Save by OK” Mode
By default, the GRAFIK Eye
®
QS control
unit is in “Save by OK” mode, which
allows you to quickly set scenes without
entering program mode.
1. Press the button for the scene you want
to set; its LED will light and the lights will
go to the current settings.
2. Use the zone raise/lower buttons to set
all lights to the desired levels. Press the
“OK” button to select.
3. Set the fade time to the desired length
using the Master buttons, and press the
“OK” button to save.
4. The info screen will confirm that the new
scene settings have been saved.
Notes
• Using the Master buttons to raise or
lower lighting settings is still temporary.
• To set a zone to unaffected (---), press
and hold the zone lower button for
6 seconds after the zone has gone to 0%
light level.
Zone raise/lower buttons