background image

®

GRAFIK Eye

®

 QS Control Unit Installation and Operation Guide   60

Afterhours (continued)

Setting Up Afterhours

1.  Enter programming mode.
2.  Use the Master buttons to highlight “Timeclock,” and press 

the “OK” button to accept.

3.  Use the Master buttons to highlight “Afterhours setup,” and 

press the “OK” button to accept.

4.  Use the Master buttons to select the desired “Afterhours” 

mode, and press the “OK” button to accept.

5.  (If the “Afterhours” mode was set to “Enabled”) 

Use the Master buttons to highlight the desired values for 
Flash count, Delay to off, Delay to flash, and Afterhours scene. 
Press the “OK” button to accept each setting. The info screen 
will confirm that your Afterhours settings have been saved.

6.   Exit programming mode.

OK

Master 
buttons

“OK”  
button

Afterhours

Enabled

Flash count

 3

Saved

Delay to flash

       minutes

 45

Delay to off

       minutes

5

Afterhours

Scene off

Ending Afterhours

  Once activated, the Afterhours feature can 

be overridden at any time and ended through 
the programming menu.

1.  Enter programming 

mode.

2.  Use the Master 

buttons to highlight 
“Timeclock,” and 
press the “OK” button 
to accept.

3.  Use the Master 

buttons to highlight 
“End Afterhours,” and 
press the “OK” button 
to accept. The info 
screen will confirm 
that “Afterhours” mode 
is ended.

4.   Exit programming 

mode.

End afterhours

Main menu

Timeclock

Scene setup

Timeclock

Holiday

Afterhours setup

Timeclock

Содержание GRAFIK Eye QSGR-3P

Страница 1: ...cklit buttons that are easy to find and operate Model Numbers QSGRJ 3P QSGRJ 4P QSGRJ 6P QSGR 3P QSGR 4P QSGR 6P 120 V 50 60 Hz 220 240 V 50 60 Hz Unit Capacity watts 2000 W 3000 W MLV 2000 VA 1600 W...

Страница 2: ...sociating Wireless Daylight Sensors 33 Assigning Sensors 34 Calibrating Sensors 34 Labeling a Daylight Sensor optional 35 Pico Wireless Control Setup 36 Associating with a GRAFIK Eye QS Wireless Contr...

Страница 3: ...aceplate Features and Functions of the GRAFIK Eye QS Control Unit Info screen Displays status or programming functions Scene buttons With integral scene indicator LEDs Timeclock button Displays curren...

Страница 4: ...1 2 3 4 1 2 A B C 1 2 3 4 5 6 L N 12 AWG 4 0 mm2 each terminal 120 127 V or 220 240 V Distribution Panel Line Voltage Mains Cables and Load Wiring 1 2 3 4 5 6 L N Incandescent load Load controlled by...

Страница 5: ...for faceplate overhang on all sides Note 4 gang wallbox available from Lutron P N 241400 Step 2 Test load wiring Turn power OFF at the circuit breaker or fuse box Connect a standard light switch betw...

Страница 6: ...to properly recognize them Notice Risk of damage to unit GRAFIK Eye QS control units must be installed by a qualified electrician in accordance with all applicable regulations and building codes Impro...

Страница 7: ...ot connect terminal 2 between any GRAFIK Eye QS control unit and any other power supply including another GRAFIK Eye QS control unit Refer to the QS Link Power Draw Units specification submittal Lutro...

Страница 8: ...Control Wiring Details QS smart power panel LUTRON LUTRON LUTRON LUTRON LUTRON T Tap Wiring Example GRAFIK Eye QS control unit Sivoia QS shade drape seeTouch QS wallstation LUTRON LUTRON LUTRON LUTRO...

Страница 9: ...ly is required to power more than 3 wallstations To power source QSPS P1 1 50 powers up to 8 seeTouch QS wallstations The Common wire from the power supply connects to QS link terminal 1 on all of the...

Страница 10: ...ins wiring 2 Verify installation Restore power Press the top scene button The LED will light Press the zone raise and lower buttons Make sure the control unit is dimming all connected loads 3 Apply th...

Страница 11: ...ows fade time adjustment In Save by OK mode pressing a second time allows zone adjustment pressing a third time allows fade adjustment The Timeclock button activates the info screen and displays the c...

Страница 12: ...Sivoia QS shades All shades fully open All shades to 50 All shades fully closed Lower Raise all shades Applies only to units with shade keypads The GRAFIK Eye QS control unit controls most lighting lo...

Страница 13: ...y to toggle between full on and off Press and hold lower for 6 seconds after the zone has gone to 0 light level to set the zone as unaffected in the current scene The zone will not change when this sc...

Страница 14: ...K button chooses the current highlighted menu choice This will either take you to the next menu or accept a setting you have selected When the screen displays a Yes No question the OK button is Yes Ti...

Страница 15: ...18 m line of sight When used within a RadioRA 2 system the wired QS link on the GRAFIK Eye QS control unit is disabled and certain features that do not pertain to RadioRA 2 are not accessible Wireles...

Страница 16: ...Non Dim Load Types Zones assigned to non dim loads have five available configurations LOFO Last On First Off FOFO First On First Off FOLO First On Last Off LOLO Last On Last Off 60 40 On at 60 off at...

Страница 17: ...25 W 220 240 V 40 W Maximum zone loads 120 127 V 800 W 220 240 V 1200 W Maximum total lighting load for magnetic low voltage MLV varies by input voltage 120 127 V 800 VA 600 W 220 240 V 1200 VA 960 W...

Страница 18: ...opriate high and low end settings please contact LutronR Technical Support for assistance High and low end trim settings limit the maximum and minimum output of a dimming zone Trim levels are set auto...

Страница 19: ...return the zone label to the default e g Zone 1 6 Use the Master buttons to scroll through the characters lowercase and uppercase letters plus numbers 0 through 9 The character you are currently chan...

Страница 20: ...e will be lit to indicate this zone is unaffected by the scene the zone will not change when this scene is initiated When all zones are at the desired level press the OK button to accept 5 Use the Mas...

Страница 21: ...ress OK for any remaining characters Press the OK button to accept 7 The info screen will confirm that your name has been saved 8 Exit programming mode Main menu Timeclock Scene setup Labels Select sc...

Страница 22: ...ogramming mode 2 Use the Master buttons to highlight Save mode and press the OK button to accept 3 Use the Master buttons to highlight the desired save mode The save modes are listed and explained bel...

Страница 23: ...revents the user from making any changes to the control unit The current scene will stay on until the CCI enables normal operation Never Save Prevents any changes from being saved while the CCI is bei...

Страница 24: ...open release has no effect Second contact closure ends Afterhours Changing the type of contact closure input 1 Enter programming mode 2 Use the Master buttons to highlight CCI Setup and press the OK...

Страница 25: ...k Wireless Occupancy Sensor The following steps are required to program occupancy sensors with a GRAFIK Eye QS control unit 1 Connect wired sensors or associate wireless sensors 2 Choose the mode of o...

Страница 26: ...s programming from the GRAFIK Eye QS control unit 7 Repeat the above steps for all desired sensors 8 Exit programming mode Associating wireless occupancy sensors through QS Sensor Modules QSM 1 Press...

Страница 27: ...in multiple areas within a room Up to four sensors can be assigned to each zone a sensor can be assigned to more than one zone to send the zones to configurable occupied and unoccupied levels 1 Enter...

Страница 28: ...nsors Note If wireless sensors are not found verify that they are associated correctly Setting the Sensor Action 1 Press the Timeclock back button to return to the Occ Sensor screen Use the Master but...

Страница 29: ...r additional sensors Note If wireless sensors are not found verify that they are associated correctly Setting the Sensor Action 1 Press the Timeclock back button to return to the Occ Sensor screen Use...

Страница 30: ...to select 6 Use the Master buttons to scroll through the characters lowercase and uppercase letters plus numbers 0 through 9 The character you are currently changing will be underlined on the screen...

Страница 31: ...led Range Disabled or 1 30 minutes default Disabled Zone Fade When in Zone Mode lights can be set to fade to the unoccupied levels over this period of time Range 0 59 seconds 1 10 minutes default 10 s...

Страница 32: ...be recognized by a GRAFIK Eye QS wireless system Daylight Sensor Setup LUTRON LUTRON LUTRON LUTRON GRAFIK Eye QS control unit GRAFIK Eye QS control unit GRAFIK Eye QS control unit QS Sensor Module QSM...

Страница 33: ...ing so will remove its programming from the GRAFIK Eye QS control unit 7 Repeat the above steps for all desired sensors 8 Exit programming mode Associating wireless daylight sensors through QS Sensor...

Страница 34: ...ireless Radio Powr SavrTM daylight sensors associated with the desired zones into Calibrate Mode Press and hold the Cal button for 6 seconds until the sensor flashes Note After 5 minutes Calibrate Mod...

Страница 35: ...o select 6 Use the Master buttons to scroll through the characters lowercase and uppercase letters plus numbers 0 through 9 The character you are currently changing will be underlined on the screen Pr...

Страница 36: ...t levels on assigned zone as preset Scene 2 Raise Lower Buttons if available Vary intensity of all assigned zones Vary intensity of all zones affected by current scene Bottom Off Button All assigned z...

Страница 37: ...wish to control with the Pico wireless control 3b To program other Pico wireless control buttons not including Raise Lower press the desired button and repeat step 3a OR 4 To assign the Pico wireless...

Страница 38: ...to select Zone and press the OK button to accept 5a Use the zone raise lower buttons for a zone to select a desired preset level and then press the zone raise and lower buttons simultaneously for 1 s...

Страница 39: ...R programming commands please see www lutron com qs An IR remote can also indirectly control the GRAFIK Eye QS control unit through the QS IR Eye or a Lutron IR receiver wired to a QS Sensor Module QS...

Страница 40: ...o highlight IR Setup and press the OK button to accept 3 Use the Master buttons to highlight Integral IR and press the OK button to accept 4 Use the Master buttons to highlight either Enabled or Disab...

Страница 41: ...ye has been associated Press the OK button to continue 3 Use the Master buttons to select Scene and press the OK button to accept 4 Use the Master buttons to select one of the scene control types list...

Страница 42: ...sh to assign to the QS IR Eye The info screen will confirm that your settings have been saved OR 2b To assign the QS IR Eye as a scene controller use the Master buttons to select Scene and press the O...

Страница 43: ...buttons to select Zone and press the OK button to accept Use the zone raise lower buttons for a zone to select a desired preset level then press the zone raise and lower buttons simultaneously for 1...

Страница 44: ...ess shade drape EDU LED For Wireless Sivoia QS Shades To associate shades with a shade button group 1 Make sure the wireless mode of the GRAFIK Eye QS control unit is Enabled 2 On the GRAFIK Eye QS co...

Страница 45: ...on which moves through the assigned EDUs in the opposite order 3 Adjust the currently selected EDU to the desired level for the open limit the maximum the shade is allowed to open using the raise and...

Страница 46: ...ons The LEDs next to the buttons will flash EDUs for the assigned shades will move to their closed limits and EDUs for unassigned shades will move to their open limits 2 Press and release the middle b...

Страница 47: ...ough the characters lowercase and uppercase letters plus numbers 0 through 9 The character you are currently changing will be underlined on the screen Press OK to select the character you want then re...

Страница 48: ...use the master buttons to highlight Stop If Moving and press OK to accept 4 For the desired shade column on bottom left of QSG unit press the Open button to enable Stop If Moving for that column or p...

Страница 49: ...to accept 4 The Info screen will display a confirming Saved message 5 Exit Programming mode Press and hold the top and bottom Scene buttons simultaneously for 3 seconds The Info screen will go to Sce...

Страница 50: ...it the maximum the shade is allowed to open 5 Press and hold the Open button for 5 seconds to store the current position as the upper limit The Open button LED will flash quickly for 2 seconds 6 Set t...

Страница 51: ...ote The wireless signal has a range of 30 ft 9 m through standard construction or 60 ft 18 m line of sight To associate two GRAFIK Eye QS control units 1 Begin with the GRAFIK Eye QS control unit that...

Страница 52: ...d press the OK button to accept 5 Use the Master buttons to highlight the current hour and press the OK button to accept Repeat for the current minutes 6 Use the Master buttons to highlight the curren...

Страница 53: ...allation and Operation Guide 53 Timeclock Operation continued Setting Location 1 Enter programming mode 2 Use the Master buttons to highlight Timeclock and press the OK button to accept 3 Use the Mast...

Страница 54: ...ices without affecting the space it controls 6 Use the Master buttons to highlight the type of the event fixed time of day or a relative time to sunrise or sunset Press the OK button to accept 7 For a...

Страница 55: ...t and delete otherwise press the Timeclock button to go back 7 The info screen will confirm that your event has been deleted 8 Exit programming mode Main menu Timeclock Scene setup Timeclock Copy sche...

Страница 56: ...tton Timeclock Delete schedule Holiday Add event View holiday Set holiday Holiday Set holiday 1 25 1 Feb Monday Set holiday 1 25 Feb 14 Deleting a Holiday 1 Enter programming mode select Timeclock sel...

Страница 57: ...ting all events occurring on the selected day to copy to press the OK button to accept 7 Exit programming mode OK Master buttons OK button Timeclock Delete schedule Delete events Copy schedule Copy fr...

Страница 58: ...Afterhours feature even if it receives commands from a Timeclock event contact closure input or another device on the QS link Note The Afterhours feature must be programmed to start or end through Ti...

Страница 59: ...ice worker Button press Office worker Button press Security guard Delay to off lights flash Delay to off lights flash Delay to off lights flash Delay to flash Delay to flash Delay to flash Delay to of...

Страница 60: ...s the OK button to accept each setting The info screen will confirm that your Afterhours settings have been saved 6 Exit programming mode OK Master buttons OK button Afterhours Enabled Flash count 3 S...

Страница 61: ...select Backlighting Press the OK button to accept 2 Use the Master buttons to highlight either Enabled or Disabled Press the OK button to accept The info screen will confirm that your setting has been...

Страница 62: ...only The character you are currently changing in the password will appear underlined on the info screen Press OK to select the desired character and repeat for the remaining characters The info scree...

Страница 63: ...language and press the OK button to select and save GRAFIK Eye QS Control Unit Installation and Operation Guide 63 OK Master buttons OK button Timeclock back button OK 1 2 3 4 5 6 Pull up to remove t...

Страница 64: ...ction is required Unit does not allow scene change or zone adjustments Unit is in wrong save mode Change to correct save mode QS device in system has locked the unit Check programming and state of QS...

Страница 65: ...ss devices do not control unit Wireless device has been unassigned from unit Reassign wireless device to unit Devices are not receiving power Check wireless device s battery power wiring Unit in incor...

Страница 66: ...ught on something Check and unbind shade fabric Shade moves in the opposite direction when raise lower buttons are pushed Open and close limits have been reversed Set limits correctly Shade button gro...

Страница 67: ...R IN ANY WAY RELATED TO THE INSTALLATION DEINSTALLATION USE OF OR INABILITY TO USE THE UNIT OR OTHERWISE UNDER OR IN CONNECTION WITH ANY PROVISION OF THIS WARRANTY OR ANY AGREEMENT INCORPORATING THIS...