GRAFIK Eye
®
QS Control Unit Installation and Operation Guide 24
Contact Closure Input (CCI) Setup (continued)
(wired directly to the GRAFIK Eye
®
QS control unit)
The integral contact closure input (CCI) on the back of the GRAFIK Eye
®
QS control unit
is compatible with either type of contact closure device:
Maintained (default): The GRAFIK Eye
®
QS control unit will act on both a contact
closure and a contact open/release event.
Example: “CCI Mode” set to “Afterhours.” Contact closure starts “Afterhours.”
Contact open/release ends “Afterhours.”
Momentary: The GRAFIK Eye
®
QS control unit will act on only contact closure events.
Example: “CCI Mode” set to “Afterhours.” Contact closure starts “Afterhours.”
Contact open/release has no effect. Second contact closure ends “Afterhours.”
Changing the type of contact closure input:
1. Enter programming mode.
2. Use the Master buttons to highlight “CCI Setup” and press the
“OK” button to accept.
3. Use the Master buttons to highlight “CCI Type” and press the
“OK” button to accept.
4. Use the Master buttons to highlight the type you wish the CCI
to control. Press the “OK” button to accept.
5. The info screen will confirm that your setting has been saved.
6. Exit programming mode.
Note:
The “Emergency CCI Mode” is different from the other
CCI modes in that “Emergency Mode” will activate on
a contact open/release and will deactivate on a contact
closure. The CCI must be set to “Maintained” (default) for
proper “Emergency Mode” operation.
CCI Type
Maintained
Saved
Saved
Main menu
Save Mode
CCI menu
CCI Mode
CCI Setup
CCI Type
OK
Master
buttons
“OK”
button
Timeclock
(back) button