EM58 • HS58 • HM58 POWERLINK
Figure 25 - Preset activated
You can enter the
I/O Mapping
window (see the “5.4.7 Monitoring the position
and speed values” section on page 49) and check that the
PositionValue_I6004
entry is “50”.
After executing the preset command, you are required to save the parameters in
order to store on memory the calculated offset. If you do not save the new
offset value, at next power up the system will calculate the encoder position
using the offset value previously saved. To save the parameters refer to the
following “5.4.10 Parameters storing program” section on page 55.
MAN EM58_HS58_HM58 PL E 1.1.odt
Quick reference
54 of 108