EM58 PA
4.9.2 Fault output connected to a relay
Figure 3
No encoder error = coil energized
Encoder error = coil de-energized
EXAMPLE
Vdc = +24V
R1 = 47
R1
I
Vdc
R2
I = 30 mA (current needed to energize a small relay coil)
R2 = 750
4.10 Current analogue output
+Iout delivers the current analogue signal.
After having enabled the analogue output by setting the
parameter in the
ENCODER CONFIGURATION
box of the
CONFIGURATION
page, the user is allowed to choose the type of output (either current or voltage)
by setting the desired value (CURRENT or VOLTAGE) next to the
parameter in the same box; then he has to set the output range by means of the
drop-down list in the following parameter
MAN EM58 PA E 1.1
Electrical connection
22 of 60