EM58 PA
No error
There are not active errors.
5.3.4 ENCODER CONFIGURATION box
Enable analog output
It enables / disables the analogue output. If
then the voltage signal or the current signal are not provided through the
relevant oVout or +Iout.
Default = enabled
Enable preset
It enables / disables the preset function. When this parameter is set to
ENABLED, the functions available in the
PRESET
box and the Preset input are
active and can be set; otherwise they are disabled. For any information on the
preset function refer to the “5.3.2 PRESET box” section on page 34.
Default = enabled
Positive counting direction
It allows to set whether the position information output by the encoder
increases when the shaft rotates clockwise or counter-clockwise. Clockwise and
counter-clockwise rotations are viewed from the shaft side. It is possible to
choose the following options: CW (STANDARD) and CCW (INVERTED). When the
counting direction is set to CW (STANDARD) -
CW (STANDARD)-, if the Counting direction input (see on page 24) has LOW
logic level (0Vdc) the encoder will provide the increasing count when the shaft
is turning clockwise (and the decreasing count when the shaft is turning
counter-clockwise); on the contrary if the Counting direction input has HIGH
logic level (+Vdc) the encoder will provide the increasing count when the shaft
is turning counter-clockwise (and the decreasing count when the shaft is
turning clockwise). When the option CCW (INVERTED) is set -
= CCW (INVERTED)-, if the Counting direction input has LOW logic
level (0Vdc) the encoder will provide the increasing count when the shaft is
turning counter-clockwise (and the decreasing count when the shaft is turning
clockwise); on the contrary if the Counting direction input has HIGH logic level
(+Vdc) the encoder will provide the increasing count when the shaft is turning
clockwise (and the decreasing count when the shaft is turning counter-
clockwise). For any information on the Counting direction input refer to the
“Electrical connection“ section on page 17 and in particular to the “4.12
Counting direction“ section on page 24.
MAN EM58 PA E 1.1
Software and configuration parameters
37 of 60