Installation
57
Due to our policy of continuous product innovation, some specifications may change without notice.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Connect to PV Inverter
This is an example of a 1 PV inverter connection. For multiple Home 8 connections, please refer to
"Multiple Home 8 Units or PV Inverters Connection".
y
PV inverters must support a Frequency-Drop or Frequency-Watt functions.
y
Make sure the PV inverter is a product that satisfies UL1741SA or UL1741SB.
y
Make sure that the Frequency-Drop or Frequency-Watt function is enabled in the PV
inverter configuration.
y
If the PV inverter does not support this function or the function is turned off, the product
may malfunction during the backup operation.
y
A PV inverter that does not support a Frequency-Drop or Frequency-Watt function may be
connected to a non-backup port in the SE Box or a non-backup load panel.
INFO
a
Install the circuit breaker for the PV inverter as shown in the figure. Follow local codes when
selecting the circuit breaker ampacity.