Installation
56
Due to our policy of continuous product innovation, some specifications may change without notice.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Any circuit connected to the SE Box will not be powered when disconnected from the grid. During
on-grid operation, these circuits are still metered by the internal site net metering with no additional
metering hardware required.
However, if non-backup load panels exist upstream of the SE Box, additional CTs are required. In this
case, refer to "Usage of External CTs".
Terminals
Wire Gauge
Tool Size
Strip
Length
Torque
Grid lug (L1, L2)
6 AWG ~ 300kcmil
1/4 inch Hex
32 mm (1.25
inches)
288 kgf-cm
(250 lbf·in)
Non-Backup Load
Lugs (L1, L2)
6 AWG – 250 kcmil
5/6 inch Hex
32 mm (1.25
inches)
259 kgf·cm
(225 lbf·in)
Backup Load Lugs
(L1,L2)
6 AWG – 250 kcmil
5/6 inch Hex
32 mm (1.25
inches)
317 kgf·cm
(275 lbf·in)
Large Neutral
Lugs
6 AWG – 250 kcmil
5/6 inch Hex
32 mm (1.25
inches)
Medium Neutral
Lugs
14 AWG – 2/0 AWG
Flat head
Screwdriver
(6 mm)
20 mm (3/4
inches)
2 – 2/0 AWG –
58 kgf·cm
(50 lbf·in)
6 – 4 AWG –
52 kgf·cm
(45 lbf·in)
14-8 AWG –
40 kgf·cm
(35 lbf·in)
Earth Lugs
14 AWG – 2/0 AWG
Flat head
Screwdriver
(6 mm)
20 mm (3/4
inches)
y
Refer to "SE Box Wiring: Power" for all wiring requirements and recommendations, including
wire colors and gauges.
y
Refer to "Whole Home Backup (Service Equipment)" for example system wiring diagrams.