Troubleshooting
120
Due to our policy of continuous product innovation, some specifications may change without notice.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Code
Description
Solution
B157
CRC data safety memory range warning
Contact service center
B300
Cell Voltage level of battery cell is higher
than the limit
Automatically restart after fault condition
is cleared
B301
Cell Voltage level of battery cell is lower than
the limit
Contact service center
B305
Unit voltage AD conversion multiplex fault
Automatically restart after fault condition
is cleared
B350
Discharge current level is higher than the
limit
Automatically restart after fault condition
is cleared
B351
Charge current level is higher than the limit
Automatically restart after fault condition
is cleared
B353
Discharge Atmosphere temperature level is
higher than the limit
Automatically restart after fault condition
is cleared
B354
Discharge Atmosphere temperature level is
lower than the limit
Automatically restart after fault condition
is cleared
B355
Charge Atmosphere temperature level is
higher than the limit
Automatically restart after fault condition
is cleared
B356
Charge Atmosphere temperature level is
lower than the limit
Automatically restart after fault condition
is cleared
B357
Current AD conversion multiplex fault
Automatically restart after fault condition
is cleared
B400
Discharge temperature level is higher than
the limit
Automatically restart after fault condition
is cleared
B401
Discharge temperature level is lower than
the limit
Automatically restart after fault condition
is cleared
B402
Charge temperature level is higher than the
limit
Automatically restart after fault condition
is cleared
B403
Charge temperature level is lower than the
limit
Automatically restart after fault condition
is cleared
B404
Power Terminal temperature level is higher
than the limit
Automatically restart after fault condition
is cleared
B458
MCU OSC HR error
Automatically restart after releasing fault
B459
Internal Communication Error (BCU
↔
BIC)
Automatically restart after releasing fault
B460
External Communication Error (BCU
↔
PCS)
Automatically restart after releasing fault
B461
Watchdog counter error
Automatically restart after releasing fault
B463
MCU CORE register error
Automatically restart after releasing fault
B464
MCU FPU register error
Automatically restart after releasing fault
B465
MCU VCU register error
Automatically restart after releasing fault