Installation
74
Due to our policy of continuous product innovation, some specifications may change without notice.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
SE Box Wiring: Internal Panelboard
The internal Panelboard is 200A-rated and supports 5 x 2-pole breaker spaces (10 circuits) using
Eaton BR Branch circuit breakers up to 125 A.
If an external generation panel is required for a large PV and Home 8 system, use a sub-feed lug
(Eaton, BRS225 / BRPSF225) on the internal panel board. In this case, other spaces on the internal
panelboard can not be used for the circuit breaker. Leave no breakers.
The Home 8 connection to the SE Box always requires a 40 A Circuit breaker. This breaker serves as
circuit protection for the Home 8.
Breaker sizing, connection, and installation must comply with the National Electric Code.
For more information, please refer to "Internal Panelboard and Additional Fastener".
No.
Terminals
Recommended Wire Color
Wire Gauge
a
BR Series Circuit Breaker on the
Internal Panel Board
L1 : Black, L2 : Red
Depends on the breaker
sizing
b
Neutral Terminal (Home 8, PV
Inverter) – 6 Positions
Green, Bare
8 – 6 AWG
c
Ground Terminal (Home 8, PV
Inverter) – 6 Positions
Green, Bare
8 – 6 AWG
* Use copper or aluminum conductors rated at 90 °C (194 °F).