Multiple Home 8 Units or PV Inverters
Connection
Dedicated circuit breakers are required when multiple power sources are connected to the SE Box to
meet the NEC. The dedicated circuit breakers should be located in the SE Box or load center of the
corresponding power source.
Do not connect any loads to the sub-panels of the PV or Home 8 or the internal panelboard in SE
Box.
Total Ampacity of the Home 8 and PV Inverter is
≤
200A (Whole Home
Backup)
1) The total ampacity of the breakers for the Home 8 and PV inverter should not exceed the
ampacity of the main breaker in the SE Box.
2) The ampacity of the main breaker in the backup panel should not exceed the ampacity of the
main breaker in the SE Box.
3) It is recommended that the PV CT be located in the the SE Box.