Technical Description

SIC40-TEN081110 | 98-2005210 | Version 1.0

EN

Содержание SUNNY ISLAND SIC40-MPT

Страница 1: ...Charge controller SUNNY ISLAND CHARGER Technical Description SIC40 TEN081110 98 2005210 Version 1 0 EN...

Страница 2: ......

Страница 3: ...acking List 11 3 2 Checking for Transport Damage 11 3 3 Identification of the Charge Controller 12 4 Mounting 13 4 1 Selection of Mounting Location 13 4 1 1 Dimensions 13 4 1 2 Ambient Conditions 14 4...

Страница 4: ...n of the Charge Controller 31 6 1 1 Operating Mode 31 6 1 2 Battery System 32 6 1 3 Device Address 32 6 1 4 Battery Type 33 6 2 Commissioning 33 7 Opening and Closing 34 7 1 Opening the Charge Control...

Страница 5: ...al Description SIC40 TEN081110 5 11 Explanation of the LEDs With Codes 41 11 1 Multicolored LED 41 11 2 Internal LEDs 41 12 Decommissioning 42 12 1 Disassembly 42 12 2 Packaging 42 12 3 Storage 42 12...

Страница 6: ...SMA Solar Technology AG 6 SIC40 TEN081110 Technical Description...

Страница 7: ...ing Sunny Island Charger type SIC40 MPT The device type of your charge controller is specified on the type label as shown in section 3 3 Identification of the Charge Controller Page 12 1 2 Target Grou...

Страница 8: ...ided will result in death or serious injury WARNING WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION CAUTION indicates a hazardous situation...

Страница 9: ...Do not connect any energy sources other than PV modules to the charge controller As soon as you begin planning the PV system ensure that the values comply with the permitted operating range of all co...

Страница 10: ...put power of the PV generator In this regard observe the limits specified by the module manufacturer Appropriate usage also includes observing all the documentation 2 2 General Safety Instructions DAN...

Страница 11: ...e controller for visible external damage such as cracks in the housing Please contact your dealer if you find any damage Object Number Description A 1 Charge controller B 1 EC Declaration of Conformit...

Страница 12: ...logy AG 12 SIC40 TEN081110 Technical Description 3 3 Identification of the Charge Controller You can identify the charge controller by the type label The type label is on the right side of the housing...

Страница 13: ...ife due to fire or explosion The charge controller housing can become hot during operation Do not mount the charge controller on flammable construction materials Do not mount the charge controller in...

Страница 14: ...60 C to guarantee optimal operation Do not expose the charge controller to direct sunlight to avoid a power reduction due to excessive heating 4 1 3 Safety Clearances Observe the following safety cle...

Страница 15: ...1 4 Position Vertical installation or tilted backwards by max 45 Install at eye level to allow operating modes to be read at all times Never install the device with a forward tilt Do not install hori...

Страница 16: ...he holes diameter at least 8 mm at the marked positions and use wall anchors at least M8 3 Screw the charge controller with its three mounting plates on the wall Use fastening material suitable for th...

Страница 17: ...allel to one another short circuits can result if the cable insulation becomes damaged Lay all cables separately NOTICE Electrostatic discharges can damage the charge controller Ground yourself before...

Страница 18: ...of the PV generator C BAT connection terminal for BAT cable of the battery D BAT connection terminal for BAT cable of the battery E Thermal fuses F EARTH connection terminal for grounding G Connectio...

Страница 19: ...terminal B 4 Tighten the lock nut of the cable screw connection L Slot for communication interface M Socket for communication interface connection N M20 metric thread cable screw connections for the...

Страница 20: ...are typical for short circuit currents between 2 000 A and 10 000 A A grounding conductor with a 16 mm 2 cross section is thus adequate for short circuit currents up to 10 000 A DANGER Danger to life...

Страница 21: ...ably damage it Never connect several charge controllers in parallel on the side of the PV generator Maximum input voltage Maximum input current 140 V DC 40 A DC Disconnection terminal between the PV g...

Страница 22: ...ad cable screw connection s lock nut D and pull it over the PV cable of the the PV generator 6 Pull the PV cable of the PV generator through the cable screw connection into the inside of the charge co...

Страница 23: ...The battery size depends on the connected PV power Observe the following table Nominal battery voltage Battery size per kWp PV 48 V min 100 Ah kWp PV 24 V min 200 Ah kWp PV 12 V min 400 Ah kWp PV Exce...

Страница 24: ...etric thread cable screw connection s lock nut B and slide it over the BAT cable of the battery 6 Pull the BAT cable of the battery through the cable screw connection into the inside of the charge con...

Страница 25: ...the poles of the DC cables are reversed replace the thermal fuses If the DC cables are reversed when connecting the thermal fuse will be irreparably damaged Proceed as described in section 9 1 Replac...

Страница 26: ...ly clicks into place 5 5 2 Connection of the Communication Interface 1 Remove the metric thread cable screw connection s lock nut A and slide it over the communication interface cable RJ45 cable provi...

Страница 27: ...to the next charge controller in this case the second charge controller and insert it into the RJ45 socket of the communication interface Follow the same procedure for the first two charge controllers...

Страница 28: ...e the signalling contact cable through a cable opening into the seal insert 4 Insert the seal insert along with signalling contact cables into the cable screw connection 5 Pull the signalling contact...

Страница 29: ...arging In the Stand alone operation operating mode a battery temperature sensor must be connected Otherwise the battery may be overcharged or insufficiently charged if temperatures outside of the temp...

Страница 30: ...screw connection s lock nut A and slide it over the battery temperature sensor cable 3 Remove the seal insert along with the cable gland from the cable screw connection 4 Route the cables through the...

Страница 31: ...the switch position of the DIL switch Assignment of the DIL Switch The DIL switches have the following assignment 6 1 1 Operating Mode The operating mode is set using the D4 DIL switch The following...

Страница 32: ...following table displays the switch position of the device addresses Switch 12 V battery system 24 V battery system 48 V battery system C1 ON OFF OFF C2 OFF ON OFF C3 OFF OFF ON Stand alone Operation...

Страница 33: ...crews 3 Connect the cables leading from the charge controller to the battery on the battery 4 Switch on the line circuit breaker and the disconnection unit 5 The LED changes its color from red to gree...

Страница 34: ...2 Carefully insert the multicolored LED into the LED socket in the charge controller 3 Close the charge controller Fasten the lid to the housing using four screws 4 Switch on the line circuit breaker...

Страница 35: ...tion During stand alone operation or during operation with the Sunny Islands 3324 4248 the charge controller automatically controls the charging voltage of the battery depending on the battery type se...

Страница 36: ...slots A 3 Insert the new thermal fuses included in the packing list 4 Close the charge controller as described in section 7 2 Closing the Charge Controller Page 34 9 2 Cleaning the Cooling Fins It is...

Страница 37: ...Parameter name Range Unit Description 141 SIC40 Total 141 01 TotSicPvPwr W Total output of all charge controllers 141 02 TotSicBatCur A Battery current of all charge controllers 142 SIC40 1 142 01 Sic...

Страница 38: ...Vtg V PV voltage of the third charge controller 144 03 Sic3BatVtg V Battery voltage of the third charge controller 144 04 Sic3BatCur A Battery current of the third charge controller 144 07 Sic3HsTmp C...

Страница 39: ...851 Sic1BatShort Pole of battery connection is reversed or short circuit on the first charge controller W852 Sic1BatVtgHi Battery overvoltage 65 V on the first charge controller W853 Sic1PvVtgHi Overv...

Страница 40: ...harge controller W876 Sic3TmpHi Device overtemperature on the third charge controller W877 Sic3ComLoss Communications loss on the third charge controller for more than 24 h W881 Sic4BatShort Pole of b...

Страница 41: ...tery voltage Red failure error Orange low PV voltage PV voltage battery voltage Internal LEDs The internal LEDs are located inside the charge controller and are only visible to the installer Yellow ER...

Страница 42: ...nger available you can also use an equivalent box that fulfills the following requirements suitable for loads of up to 10 kg can be closed fully 12 3 Storage Store the charge controller in a dry place...

Страница 43: ...ge range 12 V 24 V 48 V 25 V 60 V 40 V 80 V 70 V 100 V Number of MPP trackers 1 Max PV current for 12 V 24 V 48 V system 40 A 40 A 30 A PV current control unit MPPT coarse current control in minute cy...

Страница 44: ...lf contained lead batteries Max charging current 12 V 24 V 48 V 50 A 50 A 40 A Permanent charging current 12 V 24 V 48 V 50 A 50 A 40 A Charge control IUoU Clamping position screw terminals Recommende...

Страница 45: ...A de Display screen 1 x multicolored LED Method of installation suspended Setting the parameters Plug and Play in combination with Sunny Island CAN Piggy Back required DIL switch by stand alone applic...

Страница 46: ...rvoltage battery disconnection UBat 65 V Undervoltage battery disconnection 8 V reconnection 8 5 V Short circuit PV disconnection Short circuit battery disconnection Reverse polarity PV disconnection...

Страница 47: ...require the following information in order to provide you with the necessary assistance series number of the charge controller number of additional charge controllers type and number of modules conne...

Страница 48: ...Contact SMA Solar Technology AG 48 SIC40 TEN081110 Technical Description...

Страница 49: ...SMA Solar Technology AG Contact Technical Description SIC40 TEN081110 49...

Страница 50: ...Contact SMA Solar Technology AG 50 SIC40 TEN081110 Technical Description...

Страница 51: ...d instructions contained in all documents relevant to the product Operating the product under incorrect safety or protection conditions Altering the product or supplied software without authority The...

Страница 52: ...SMA Solar Technology AG Sonnenallee 1 34266 Niestetal Germany Tel 49 561 9522 4000 Fax 49 561 9522 4040 E Mail Vertrieb SMA de Freecall 0800 SUNNYBOY Freecall 0800 78669269 www SMA de...