![SMA SUNNY ISLAND SIC40-MPT Скачать руководство пользователя страница 46](http://html1.mh-extra.com/html/sma/sunny-island-sic40-mpt/sunny-island-sic40-mpt_technical-description_1294206046.webp)
Technical Data
SMA Solar Technology AG
46
SIC40-TEN081110
Technical Description
SIC40-MPT
Security
Device overtemperature
derating / disconnection
Device undertemperature
disconnection at –30 °C
Overvoltage (PV)
disconnection >140 V
Undervoltage (PV)
disconnection at U
PV
< U
Bat
;
reconnection U
PV
= U
Bat
+5 V
Overvoltage (battery)
disconnection U
Bat
> 65 V
Undervoltage (battery)
disconnection < 8 V; reconnection > 8.5 V
Short circuit PV
disconnection
Short circuit battery
disconnection
Reverse polarity PV
disconnection
Reverse polarity battery
fuse trips
Displays
Operation display
multicolored LED
Transmission data display
internal LED (not visible from the outside)
Data reception display
internal LED (not visible from the outside)
Display on the Sunny Island
battery current, PV power, PV voltage,
operating mode, error