11
Indoor unit communication error
Error
No.
Error Type
Error Point
Main Reasons
Indoor unit doesn’t get sig-
nal from ODU for 3 minutes
continuously
1. Indoor 485 communication PCB fault
2. After PCB replacing, auto addressing
was not done
■
Error diagnosis and countermeasure flow chart
Yes
No
After Auto addressing,
error code disappears?
Replace indoor unit 485
communication PCB
No
After ODU main PCB
reset, error code
disappears?