3.1.2 Pressure control on heating mode
■
High pressure control
■
Low pressure control
❈
Frequency holding : frequency (or RPM) is not increasing ( can decrease )
Pressure Range
Compressor
Fan
Hot_gas
P
d
≥
4003 kPa (580.6 psi)
Stop
Stop
On
P
d
> 3676 kPa (533.2 psi)
-5Hz/4sec.
1)
-50RPM/4sec.
On
P
d
≤
3448 kPa (500.1 psi)
Normal control
Normal control
P
d
≤
Target press
Normal control
off
Pressure Range
Compressor
Fan
Hot_gas
P
s
≤
229 kPa (33.2 psi)
after 1min
Stop
Stop
On
P
s
≤
229 kPa (33.2 psi)
1min
-5Hz/4sec.
+100RPM/4sec.
P
s
≤
242 kPa (35.1 psi)
Frequency holding
Normal control
P
s
≤
268 kPa (38.9 psi)
Normal control
P
s
> 307 kPa (44.5 psi)
Off
2
1
3
Function
3.1 Pressure protection control
3.1.1 Pressure control on cooling mode
■
High pressure control
■
Low pressure control
❈
Frequency holding : frequency (or RPM) is not increasing ( can decrease )
3. Protection control
Pressure Range
Compressor
Fan
Hot_gas
P
d
≥
4003 kPa (580.6 psi)
Stop
Stop
-
P
d
> 3676 kPa (533.2 psi)
-5Hz/4sec.
+100RPM/4sec.
P
d
≥
3448 kPa (500.1 psi)
Frequency holding
Normal control
P
d
< 3284 kPa (476.3 psi)
Normal control
-
Pressure Range
Compressor
Fan
Hot_gas
P
s
≤
229 kPa (33.2 psi)
after 1min
Stop
Stop
On
P
s
≤
229 kPa (33.2 psi)
1min
-5Hz/4sec.
-100RPM/4sec.
P
s
≤
242 kPa (35.1 psi)
Normal control
Normal control
P
s
≥
399 kPa (57.9 psi)
Normal control
Off