Troubleshooting Guide
- 117 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
1. CT sensor defect
2. Capacity over of AVR
Error No.
Error Type
Error Point
Main Reasons
During operation(compressor fre-
quency is over 50Hz), difference
between R & T phase is 5A for 10
seconds.
3 Phase Power Unbalance
74*
Master 741
Slave 742
■
Error Diagnosis and Countermeasure Flow Chart
Recheck power and
installing condition
Yes
Is inverter PCB assembly
power wiring normal?
Check abnormal wiring between Inverter PCB assembly & bridge diode
(misconnection,disconnection)
→
Rewiring if abnormal wiring found
No
Yes
Is input voltage normal?
Check
R~S/S~T/T~R Phase voltage : 460V
±
10% (3Ø 460V)
208/230V
±
10% (3Ø 208/230V)
→
Check connection condition and wiring if power is abnormal
No
Yes
Does indoor unit power
bridge R,S,T phase equally?
Bridge R-N,S-N,T-N voltage equally (3Ø 460V)
No
Yes
Is inverter PCB
assembly normal?
Replace inverter PCB assembly
No
Measuring input voltage
Checking joining condition
Inverter PCB & Bridge Diode wiring