Troubleshooting Guide
- 90 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
23*
Master
231
Slave
232
Inverter Compressor DC
Link Low Voltage
Error
No.
Error Type
Error Point
Main Reasons
DC Voltage isn't charged
after starting relay on
1. DC Link terminal misconnection/terminal
contact fault
2. Starting relay damage
3. Condenser damage
4. Inverter PCB assembly damage
(DC Link voltage sensing part)
5. Input voltage low
■
Error Diagnosis and Countermeasure Flow Chart
Is input voltage normal?
No
Yes
Yes
Yes
Recheck power and installation condition
Check
R~S/S~T/T~R Phase voltage : 460V
±
10% (3Ø 460V)
208/230V
±
10% (3Ø 208/230V)
→
Check connection condition and wiring if power is
abnormal
Is inverter PCB assembly
power connection normal?
No
Check connection between inverter PCB assembly and
bridge diode(misconnection, disconnection)
→
wiring again if abnormality found
Is inverter PCB assembly normal?
No
Check inverter PCB assembly IPM normality
→
Replace inverter PCB assembly