Troubleshooting Guide
- 126 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
1. Wrong connection between Inverter and
Fan PCB
2. Fan PCB power not supplied
3. ODU Inv/Fan PCB defect
Error No.
Error Type
Error Point
Main Reasons
Fan controller didn't receive signal
from inverter controller
Transmission error
(Fan PCB
↔
Inverter
PCB)
105*
Master
11
→
051
Slave
12
→
052
■
Error Diagnosis and Countermeasure Flow Chart
1. Check DC 15V power cable between Inverter PCB and fan PCB
2. Check communication cable between Inverter PCB and fan PCB
→
Reconnect or replace wire if abnormality found
Check communication cable between Inverter PCB and fan PCB
→
Reconnect or replace wire if abnormality found
Yes
No
Yes
No
Is fan PCB communication
LED(yellow) blinking
normally?
Is inverter PCB
communication LED(yellow)
blinking normally?
Yes
Is fan PCB assembly normal?
Recheck power and
installation condition
No
Fan communication
connection
Communication connector
Communication LED
Checking 15V input
Replace inverter PCB assembly
❈
Note : Check fan PCB assembly Error LED blinking (Check 108
π
¯ Error)
Fan Error LED
Fan PCB assembly
Yes
No
Error LED