Troubleshooting Guide
- 129 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
1. Defective temperature sensor con-
nection
2. Defective temperature sensor
(Open / Short)
3. Defective outdoor unit PCB
Error No.
Error Type
Error Point
Main Reasons
Abnormal sensor resistance value
(Open/Short)
Outdoor unit liquid pipe
(condenser) temperature
sensor error
113*
Master
11
→
131
Slave
12
→
132
1. Defective temperature sensor con-
necter connection
2. Defective temperature sensor
(Open/Short)
3. Defective outdoor PCB
Error No.
Error Type
Error Point
Main Reasons
Abnormal sensor resistance value
(Open/Short)
Outdoor unit sub-cooling
inlet / outlet temperature
sensor error
114*
Master
11
→
141
Slave
12
→
142
■
Error diagnosis and countermeasure flow chart
Is temperature sensor
connector connections
are normal?
Is the value of temperature
sensor resistance normal?*
Check and correct connection
Replace sensor
Replace outdoor unit PCB
Yes
Yes
No
No
* Sensor resistance 100 k
Ω
over (open) or 100
Ω
below (short) will generate error
Note: Temperate sensor resistance vary with temperature, So compare temperature sensor resistance value
according to outdoor unit temperature by referring below table (±5% tolerance)
Air temperature sensor: 10°C(50°F) = 20.7 k
Ω
, 25°C(76°F) = 10 k
Ω
, 50°C(122°F) = 3.4 k
Ω
Pipe temperature sensor: 10°C(50°F) = 10 k
Ω
, 25°C(76°F) = 5 k
Ω
, 50°C(122°F) = 1.8 k
Ω