Troubleshooting Guide
- 114 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
71*
Master
711
Slave
712
Inverter input current CT
sensor error
Error
No.
Error Type
Error Point
Main Reasons
Micom input voltage isn't
within 2.5V ±0.3V at initial
state of power supply
1. Input voltage abnormal
2. ODU inverter PCB damage
(CT sensing part)
■
Error Diagnosis and Countermeasure Flow Chart
Is input voltage normal?
No
Yes
Recheck power and installation condition
Is inverter PCB assembly normal?
No
Yes
Check
R~S/S~T/T~R Phase voltage : 460V
±
10% (3Ø 460V)
208/230V
±
10% (3Ø 208/230V)
→
Check connection condition and wiring if power is
abnormal
Replace inverter PCB assembly
* Measuring input voltage
Содержание ARUN Series
Страница 134: ...P NO MFL50459503 MAY 2008 ...