2.2 Defrost
Defrost operation eliminates ice attached on heat exchanger, recovering performance of heat exchanger.
Each cycle component operates as following table during defrost operation.
■
Ending condition
1) All heat exchanger pipe temperature are above 15°C(58°F)(UY2) or 20°C(68°F)(UW1) for 30 sec.
2) The running time of defrost operation is over 30% of the total heating time
3) If compressor protection control starts by high discharge temperature of compressor etc.