Function
2.3 Stopping operation
2.3.1 Stopping operation on cooling mode
2.3.2 Stopping operation on heating mode
After 15 min.
(Before 15 Min. : ON)
-
After 15 min.
(Before 15 min. : Min. pulse)
After 15 min.
(Before 15 min. : Min. pulse)
-
-
-
Note
OFF
OFF
Max. pulse
Max. pulse
Stop
OFF
0Hz
Operation
Hot gas bypass valve
4way valve
Subcooling EEV
Main EEV
FAN
Constant Speed Compressor
Inv Compressor
Component
After 15 min.
(Before 15 Min. : ON)
After 60 min.
After 15 min.
(Before 15 min. : Min. pulse)
After 15 min.
(Before 15 min. : Min. pulse)
-
-
-
Note
OFF
OFF
Max. pulse
Max. pulse
Stop
OFF
0Hz
Operation
Hot gas bypass valve
4way valve
Subcooling EEV
Main EEV
FAN
Constant Speed Compressor
Inv Compressor
Component