2.1 Oil return control
2.1.1 Oil return control on cooling mode
Oil return operation recovers oil amount in compressor by collecting oil accumulated in pipe.
Each cycle component operates as following table during oil return operation.
■
Oil return operation time : 3 min for running step
■
Starting condition:every 6 hours operate
■
Oil return process ends if compressor protection control starts
Normal control
OFF
100 pulse
Max. pulse
Normal control
OFF
40Hz
Ending
Normal control
OFF
Main. pluse
Max. pulse
Normal control
ON
Setting Value
Running
Normal control
OFF
Normal control
Max. pulse
Normal control
OFF
25Hz
Starting
Hot gas bypass valve
4way valve
Subcooling EEV
Main EEV
FAN
Constant Speed Compressor
Inv Compressor
Component
OFF
Min. pulse
Normal control
Normal control
Ending
ON
1200 pulse
1200 pulse
OFF
Running
OFF
Min. pulse
Normal control
Normal control
Starting
Oil return signal
Thermo off unit EEV
Thermo on unit EEV
Fan
Component
Outdoor Unit
Indoor Unit
2. Special control