Troubleshooting Guide
- 108 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
1. Power cable or communication cable is not
connected
2. Defect of outdoor Main fuse/Noise Filter
3. Defect of outdoor Main / inverter PCB
Error
No.
Error Type
Error Point
Main Reasons
Main controller of Master
unit of Master unit can’t
receive signal from
inverter controller
Communication error
between
(Inverter PCB
➔
Main PCB)
52*
Master 521
Slave 522
■
Error diagnosis and countermeasure flow chart
Communication connector & LED in MAIN PCB
Communication connector & LED in inverter compressor PCB
Is communication
LED (Yellow) of inverter
compressor
PCB on?
Yes
No
Is noise filter or fuse
normal?
Replace noise filter or fuse
No
Replace inverter compressor PCB
Is communication cable
connected correctly?
Yes
No
Re-connect communication cable
Is MAIN PCB normal?
Yes
No
Replace MAIN PCB
Replace inverter compressor PCB
* The method of checking MAIN PCB and inverter compressor PCB (If normal, communication LED blinks)
Yes