Function
3.2 Discharge temperature control
■
Outdoor unit control
■
Indoor unit control
3.3 Inverter protection control
❈
AC input current is inverter input current except constant speed compressor current(Noise filter passed current)
Emergency
SH control
System stop
103
°
C(217
°
F) <
Tdis
≤
112
°
C(234
°
F)
Tdis > 115
°
C(239
°
F)
Temperature range
EEV
Keep current control
98
°
C(208
°
F) < Tdis
≤
103
°
C(217
°
F)
SH control
Tdis
≤
98
°
C(208
°
F)
Frequency down +
const. Comp off
Liquid injection on
No frequency up
System stop
105
°
C(221
°
F) <
Tdis
≤
112
°
C(234
°
F)
Tdis > 115
°
C(239
°
F)
Temperature range
Compressor
On
Liquid injection
Keep state
OFF
(below 20
°
C(212
°
F))
Pressure control
Tdis
≤
98
°
C(208
°
F)
Off
Max. limit
490 pulse
Max. limit
490 pulse
Subcooling EEV
Max. limit
300 pulse
Pressure control
Tdis > 95
°
C(203
°
F)
Off
10 pulse open /10sec
30A or more
28A or more
28A or less
Compressor Current
20A or more
18A or more
18A or less
AC Input Current
System Stop
Frequency Down
Normal Operation
98
°
C(208
°
F) <
Tdis
≤
103
°
C(217
°
F)