1. Caution For Refrigerant Leaks
3
Multi V 5
Special Guide
1.2.2 Calculate refrigerant concentration level
Calculate the volume of the room where indoor unit is installed as single room or the smallest room.
1. Without partition
2. With partition but opened which serve passage of air to adjoining room
3. With partition and without opening which serve as passage of air to adjoining room
Calculate refrigerant concentration
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Opening
Partition
In the case of opening
without door , or 0.15
% or more openings
(to floor space) both
above and below door)
Outdoor unit
Indoor unit
Smallest
room
(R410A)
(kg/m
Total amount of refrigerant
system (kg)
Volume of smallest room where
indoor unit is installed (m
Maximum concentration
limit
In case the result of calculation exceeds
the concentration limit, perform the
same calculations by shifting to the
second smallest, and the third smallest
rooms until at last the result is below the
concentration limit.
Содержание ARUM080LTE5
Страница 1: ...Heat Recovery Heat Pump R410A 50Hz 60Hz 0CVV0 01E Replaces 0CVV0 01D P No MFL67474071 ...
Страница 85: ...78 Multi V 5 Outdoor Units 4 Wiring Diagrams 4 1 8 10 12 HP UXA 1 Comp ...
Страница 86: ...4 Wiring Diagrams 79 Multi V 5 Outdoor Units 4 2 14 16 HP UXB 1 Comp ...
Страница 87: ...Multi V 5 4 Wiring Diagrams 80 Outdoor Units 4 3 18 20 22 24 26HP UXB 2 Comp ...
Страница 703: ...5 Multi V 5 Heat Recovery HR Unit 3 Dimensions PRHR023 PRHR033 PRHR043 481 176 125 311 150 150 486 500 218 40 55 19 ...
Страница 704: ...Multi V 5 Heat Recovery 3 Dimensions 6 HR Unit PRHR063 PRHR083 809 218 55 40 19 793 160 160 481 176 311 125 ...
Страница 766: ...Special Guide Multi V 5 1 Cautions for Refrigerant Leaks 2 Guide for installing at seaside ...