7. Refrigerant piping system
23
Multi V 5
Installation of Outdoor Units
■
Outdoor unit Connection
* Maximum number of connectable units could be different in accordance with model line up of target region.
A : Refrigerant pipe diameter from outdoor unit to first branch
E : Refrigerant pipe diameter for outdoor unit capacity (Slave 1+ Slave 2+ Slave 3)
F : Refrigerant pipe diameter for outdoor unit capacity (Slave 2+ Slave 3)
G : Refrigerant pipe diameter for outdoor unit capacity (Slave 3)
WARNING
•
In case of pipe diameter connected after first branch(B) is bigger than the main pipe diameter(A), B
should be of the same size with A.
•
Do not choose the main pipe diameter by downward indoor unit total capacity, but its outdoor unit model
name.
•
Do not let the connection pipe from branch to branch exceed the main pipe diameter chosen by outdoor
unit model name.
[Example 1]
In case indoor unit combination ratio 120% is connected to 24HP(67.2 kW) outdoor unit.
1. Outdoor unit main pipe diameter A : Ø34.9(Gas pipe), Ø15.88(liquid pipe)
2. Pipe diameter B after first branch according to 120% indoor unit ombination(80.6kW) : Ø34.9(gas pipe),
Ø19.05(liquid pipe)
Therefore, pipe diameter B connected after first branch would be Ø34.9(gas pipe) / Ø15.88(liquid pipe) which is
same with main pipe diameter.
[Example 2]
Where connecting the indoor units to the 22 HP (61.6 kW) outdoor unit to 130% of its system capacity
(80.1kW) and branching 7k (2.2kW) indoor unit at the 1st branch.
1. Main pipe diameter(22 HP outdoor unit): Ø28.58(gas pipe), Ø15.88(Liquid pipe)
2. Pipe diameter between 1st and 2nd branch (77.9kW indoor units) :
Ø34.9(Gas pipe), Ø19.05(Liquid pipe) in conformity with downward indoor units.
Since the main pipe diameter of 22HP outdoor unit is Ø28.58(gas pipe), Ø15.88(Liquid pipe) is used as the main
pipe and the connection pipe between 1st and 2nd branch.
Level Difference (Outdoor unit
↔
Outdoor unit)
5m [16.4ft]
Max length from first branch to each outdoor unit (L1, L2, L3)
Less than 10m [32.8ft]
(equivalent length of piping 13m [42.7ft])
L1
L2
L3
H1
l
n
m
Slave3
Slave2
Slave1
Master
l
40m
h 40m
Indoor
Unit
1st branch
Refrigerant pipe diameter from outdoor unit to first branch
d
d
d
d
d
Содержание ARUM080LTE5
Страница 1: ...Heat Recovery Heat Pump R410A 50Hz 60Hz 0CVV0 01E Replaces 0CVV0 01D P No MFL67474071 ...
Страница 85: ...78 Multi V 5 Outdoor Units 4 Wiring Diagrams 4 1 8 10 12 HP UXA 1 Comp ...
Страница 86: ...4 Wiring Diagrams 79 Multi V 5 Outdoor Units 4 2 14 16 HP UXB 1 Comp ...
Страница 87: ...Multi V 5 4 Wiring Diagrams 80 Outdoor Units 4 3 18 20 22 24 26HP UXB 2 Comp ...
Страница 703: ...5 Multi V 5 Heat Recovery HR Unit 3 Dimensions PRHR023 PRHR033 PRHR043 481 176 125 311 150 150 486 500 218 40 55 19 ...
Страница 704: ...Multi V 5 Heat Recovery 3 Dimensions 6 HR Unit PRHR063 PRHR083 809 218 55 40 19 793 160 160 481 176 311 125 ...
Страница 766: ...Special Guide Multi V 5 1 Cautions for Refrigerant Leaks 2 Guide for installing at seaside ...