Multi V 5
7. Refrigerant piping system
26
Installation of Outdoor Units
7.3.4 Examples of Wrong Pipe Connections
• The pipes between the outdoor units must maintain horizontal levelness or give an inclination to prevent a back
flow toward the slave outdoor unit. Otherwise, the unit may not operate properly.
• Apply Oil Trap as shown below when the length of the pipe between the outdoor units is more than 2m(6.6ft).
Otherwise, the unit may not operate properly.
(Example 1)
(Example 2)
(Example 3)
(Example 1)
pGGGGG
GGG
GSGGG
GGG
GU
pGGGGGGG
GGGSGGG
GGGGGU
vG{
Toward indoor unit
Toward indoor unit
Toward indoor unit
Pipe inclination (2° or more)
Toward indoor unit
Toward indoor unit
Toward indoor unit
Toward indoor unit
≤
2m(6.6ft)