9
Multi V 5
Installation of Outdoor Units
5. Installation
• Install at places where it can endure the weight and vibration/noise of the outdoor unit.
• The outdoor unit support block at the bottom shall have width of at least 100mm(3-15/16inch) under the units
legs before being fixed.
• The outdoor unit support block hould have minimum height of 200mm(7-7/8inch).
• Anchor bolts must be inserted at least 75mm(2-15/16inch).
5.1 The location of the Anchor bolts
Chassis
A [mm(inch)]
B [mm(inch)]
UXA
930(36-5/8)
730(28-3/4)
UXB
1,240(48-13/16)
1,040(40-15/16)
At least 100mm
At least 100mm
At least 100mm
At least 100mm
At least 100mm
At least 100mm
Outdoor units
should not be
supported only by
the corner supports.
Center of the Unit
Center of the Unit
(3-15/16 inch)
(3-15/16 inch)
(3-15/16 inch)
(3-15/16 inch)
(3-15/16 inch)
(3-15/16 inch)
7
31(28-25/32)
7
60(29-29/32)
65
(2-9/16)
65
(2-9/16)
Unit : mm(inch)
At
least
65(2-9/16)
At
least
65(2-9/16)
Содержание ARUM080LTE5
Страница 1: ...Heat Recovery Heat Pump R410A 50Hz 60Hz 0CVV0 01E Replaces 0CVV0 01D P No MFL67474071 ...
Страница 85: ...78 Multi V 5 Outdoor Units 4 Wiring Diagrams 4 1 8 10 12 HP UXA 1 Comp ...
Страница 86: ...4 Wiring Diagrams 79 Multi V 5 Outdoor Units 4 2 14 16 HP UXB 1 Comp ...
Страница 87: ...Multi V 5 4 Wiring Diagrams 80 Outdoor Units 4 3 18 20 22 24 26HP UXB 2 Comp ...
Страница 703: ...5 Multi V 5 Heat Recovery HR Unit 3 Dimensions PRHR023 PRHR033 PRHR043 481 176 125 311 150 150 486 500 218 40 55 19 ...
Страница 704: ...Multi V 5 Heat Recovery 3 Dimensions 6 HR Unit PRHR063 PRHR083 809 218 55 40 19 793 160 160 481 176 311 125 ...
Страница 766: ...Special Guide Multi V 5 1 Cautions for Refrigerant Leaks 2 Guide for installing at seaside ...