Multi V 5
1. Specifications
20
Outdoor Units
HP
38
40
Model Name
Combination Unit
ARUM380LTE5
ARUM400LTE5
Independent Unit
ARUM240LTE5
ARUM240LTE5
ARUM140LTE5
ARUM160LTE5
Capacity
Cooling
kW
106.4
112.0
Btu/h
363,000
382,100
Heating
kW
118.4
124.7
Btu/h
403,800
425,300
Input
Cooling
kW
24.30
26.32
Heating
kW
28.52
31.19
EER
4.39
4.25
COP
4.15
4.00
Exterior
Color
Morning Gray / Dawn Gray
Morning Gray / Dawn Gray
RAL (Classic)
RAL 7030 / RAL 7037
RAL 7030 / RAL 7037
Heat Exchanger
Wide Louver Plus
Wide Louver Plus
Compressor
Type
Hermetically Sealed Scroll
Hermetically Sealed Scroll
Piston Displacement
cm
3
/rev
62.1 × 3
62.1 × 3
Number of Revolution
rev/min
3,600 × 3
3,600 × 3
Motor Output x Number
W x No.
5,300 × 3
5,300 × 3
Starting Method
Inverter
Inverter
Oil Type
FW68D(PVE)
FW68D(PVE)
Fan
Type
Propeller fan
Propeller fan
Motor Output x Number
W
900 × 4
900 × 4
Air Flow Rate(High)
m
3
/min
320 × 2
320 × 2
ft
3
/min
11,301 × 2
11,301 × 2
External Static Pressure (Max, Pa)
80
80
Drive
DC INVERTER
DC INVERTER
Discharge
Side / Top
TOP
TOP
Pipe
Connections
#1
Liquid
mm(inch)
19.05(3/4)
19.05(3/4)
Low Pressure Gas
mm(inch)
41.3(1-5/8)
41.3(1-5/8)
High Pressure Gas
mm(inch)
34.9(1-3/8)
34.9(1-3/8)
Pipe
Connections
#2
Liquid
mm(inch)
19.05(3/4)
19.05(3/4)
Gas
mm(inch)
41.3(1-5/8)
41.3(1-5/8)
Dimensions(W x H x D)
mm
(1,240 ×1,690 × 760) × 2
(1,240 ×1,690 × 760) × 2
inch
(48-13/16 × 66-17/32 × 29-29/32) × 2
(48-13/16 × 66-17/32 × 29-29/32) × 2
Net Weight
kg
(310 × 1) + (237 × 1)
(310 × 1) + (237 × 1)
lbs
(683 × 1) + (522 × 1)
(683 × 1) + (522 × 1)
Sound
Pressure Level
Cooling
dB(A)
66.2
66.3
Heating
dB(A)
68.0
68.1
Sound Power
Level
Cooling
dB(A)
89.0
89.2
Heating
dB(A)
91.0
91.2
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system
Содержание ARUM080LTE5
Страница 1: ...Heat Recovery Heat Pump R410A 50Hz 60Hz 0CVV0 01E Replaces 0CVV0 01D P No MFL67474071 ...
Страница 85: ...78 Multi V 5 Outdoor Units 4 Wiring Diagrams 4 1 8 10 12 HP UXA 1 Comp ...
Страница 86: ...4 Wiring Diagrams 79 Multi V 5 Outdoor Units 4 2 14 16 HP UXB 1 Comp ...
Страница 87: ...Multi V 5 4 Wiring Diagrams 80 Outdoor Units 4 3 18 20 22 24 26HP UXB 2 Comp ...
Страница 703: ...5 Multi V 5 Heat Recovery HR Unit 3 Dimensions PRHR023 PRHR033 PRHR043 481 176 125 311 150 150 486 500 218 40 55 19 ...
Страница 704: ...Multi V 5 Heat Recovery 3 Dimensions 6 HR Unit PRHR063 PRHR083 809 218 55 40 19 793 160 160 481 176 311 125 ...
Страница 766: ...Special Guide Multi V 5 1 Cautions for Refrigerant Leaks 2 Guide for installing at seaside ...