2
Multi V 5
Special Guide
1. Caution For Refrigerant Leaks
The installer and system specialist shall secure safety against leakage according to local regulations or standards.
The following standards may be applicable if local regulations are not available.
1.1 Introduction
Though the R410A refrigerant is harmless and incombustible itself , the room to equip the air conditioner should
be large to such an extent that the refrigerant gas will not exceed the limiting concentration even if the refrigerant
gas leaks in the room.
1.1.1 Concentration limit
1.2 Checking procedure of limiting concentration
Check concentration limit along following steps and take appropriate measure depending on the situation.
1.2.1 Calculate amount of all the replenished refrigerant (kg) per each
refrigerant system.
Concentration limit is the limit of Freon gas concentration where immediate measures can be taken without
hurting human body when refrigerant leaks in the air. The concentration limit shall be described in the unit of
kg/m3 (Freon gas weight per unit air volume) for facilitating calculation.
Concentration limit : 0.44kg/m
3
(R410A)
Outdoor unit
(No.1 system)
Flow of
refrigerant
Indoor unit
Room where refrigerant leaks
(Refrigerant of the whole No.1
system flows out.)
Amount of additional
replenished refrigerant
Total amount of refrigerant
in the system
(kg)
R
d
Note : In case one refrigerant facility is
divided into 2 or more refrigerant
systems and each system is
independent, amount of replenished
refrigerant of each system shall be
adopted.
Amount of pre-charged
refrigerant per single
system
Amount of replenished
refrigerant at factory shipment
Amount of additionally
replenished refrigerant
depending on piping
length or piping
diameter by customer
Содержание ARUM080LTE5
Страница 1: ...Heat Recovery Heat Pump R410A 50Hz 60Hz 0CVV0 01E Replaces 0CVV0 01D P No MFL67474071 ...
Страница 85: ...78 Multi V 5 Outdoor Units 4 Wiring Diagrams 4 1 8 10 12 HP UXA 1 Comp ...
Страница 86: ...4 Wiring Diagrams 79 Multi V 5 Outdoor Units 4 2 14 16 HP UXB 1 Comp ...
Страница 87: ...Multi V 5 4 Wiring Diagrams 80 Outdoor Units 4 3 18 20 22 24 26HP UXB 2 Comp ...
Страница 703: ...5 Multi V 5 Heat Recovery HR Unit 3 Dimensions PRHR023 PRHR033 PRHR043 481 176 125 311 150 150 486 500 218 40 55 19 ...
Страница 704: ...Multi V 5 Heat Recovery 3 Dimensions 6 HR Unit PRHR063 PRHR083 809 218 55 40 19 793 160 160 481 176 311 125 ...
Страница 766: ...Special Guide Multi V 5 1 Cautions for Refrigerant Leaks 2 Guide for installing at seaside ...