8. Electrical Wiring
37
Multi V 5
Installation of Outdoor Units
8.1.3 Communication and Power Lines
1.
Communication cable
• Types : shielded cables
• Use wires of size : over 1.0 ~ 1.5 mm
2
(1.55 × 10
-3
~ 2.32 × 10
-3
in
2
)
• Maximum allowable temperature: 60°C (140°F)
• Maximum allowable line length: under 1 000m (3 281 ft)
2.
Remote control cable
• Types : 3-core cable
3.
Central control cable
4.
Separation of communication and power lines
• If communication and power lines are installed alongside each other then there is a strong likelihood of
operational faults developing due to interference in the signal wiring caused by electrostatic and
electromagnetic coupling.
The tables below indicates our recommendation as to appropriate spacing of communication and power lines
where these are to be run side by side
Note
1. The figures are based on assumed length of parallel cabling up to 100 m(328 ft). For length in excess of 100
m(328 ft) the figures will have to be recalculated in direct proportion to the additional length of line involved.
2. If the power supply waveform continues to exhibit some distortion the recommended spacing in the table should
be increased.
• If the lines are laid inside conduits then the following point must also be taken into account when grouping
various lines together for introduction into the conduits
• Power lines(including power supply to air conditioner) and signal lines must not be laid inside the same
• In the same way, when grouping the lines power and signal lines should not be bunched together.
CAUTION
• If apparatus is not properly earthed then there is always a risk of electric shock, the grounding of the apparatus
must be carried out by a qualified person.
Product type
Wire type
Diameter
ACP&AC Manager
2-core cables
(shielded)
1.0 ~ 1.5 mm
2
(1.55 × 10
-3
~ 2.32 × 10
-3
in
2
)
AC Smart
2-core cables
(shielded)
1.0 ~ 1.5 mm
2
(1.55 × 10
-3
~ 2.32 × 10
-3
in
2
)
Simple central controller
4-core cables
(shielded)
1.0 ~ 1.5 mm
2
(1.55 × 10
-3
~ 2.32 × 10
-3
in
2
)
AC Ez
4-core cables
(shielded)
1.0 ~ 1.5 mm
2
(1.55 × 10
-3
~ 2.32 × 10
-3
in
2
)
Current capacity of power line
Spacing
100V or more
10A
300mm (11-13/16 in)
50A
500mm (19-11/16 in)
100A
1 000mm (39-3/8 in)
Exceed 100A
1 500mm (59-1/16 in)
Содержание ARUM080LTE5
Страница 1: ...Heat Recovery Heat Pump R410A 50Hz 60Hz 0CVV0 01E Replaces 0CVV0 01D P No MFL67474071 ...
Страница 85: ...78 Multi V 5 Outdoor Units 4 Wiring Diagrams 4 1 8 10 12 HP UXA 1 Comp ...
Страница 86: ...4 Wiring Diagrams 79 Multi V 5 Outdoor Units 4 2 14 16 HP UXB 1 Comp ...
Страница 87: ...Multi V 5 4 Wiring Diagrams 80 Outdoor Units 4 3 18 20 22 24 26HP UXB 2 Comp ...
Страница 703: ...5 Multi V 5 Heat Recovery HR Unit 3 Dimensions PRHR023 PRHR033 PRHR043 481 176 125 311 150 150 486 500 218 40 55 19 ...
Страница 704: ...Multi V 5 Heat Recovery 3 Dimensions 6 HR Unit PRHR063 PRHR083 809 218 55 40 19 793 160 160 481 176 311 125 ...
Страница 766: ...Special Guide Multi V 5 1 Cautions for Refrigerant Leaks 2 Guide for installing at seaside ...