7. Refrigerant piping system
27
Multi V 5
Installation of Outdoor Units
• Install Oil trap if the ODU is at lower level than main piping.
• When connecting the pipes between the outdoor units, the accumulation of oil in the slave outdoor unit should
be avoided. Otherwise, the unit may not operate properly.
(Example 2)
(Example 1)
(Example 2)
(Example 3)
Toward indoor unit
≤
2m(6.6ft)
≤
2m(6.6ft)
≥
0.2m(0.66ft)
Oil Trap
Toward indoor unit
Toward indoor unit
Toward indoor unit
h
Toward indoor unit
h
≥
0.2m(0.66ft)
Toward indoor unit
Oil Trap