8. Electrical Wiring
39
Multi V 5
Installation of Outdoor Units
■
Master / Slave Dip Switch Setting
Important
How to setting Heat Recovery system
1. Turn on the dip s/w No. 4.
2. The factory setting display is appeared “HP”.
3. Change “HP” into “HR” display pushing
▶
button and then push confirm button.
4. Turn off dip s/w No. 4 and push reset button to restart the system.
(If you turn on the dip s/w No. 4, you can make sure “HR” or “HP” display later.)
Dip switch setting
Master/Slave Unit
Master
Slave
Slave1
Slave2
Slave3
Heat Pump System
(Factory setting)
Heat Recovery System
(Installer setting)