3
Multi V 5
Heat Recovery
HR Unit
2. Specifications
Note
1. Voltage range : Voltage supplied to the unit terminals should be within the minimum and maximum range.
2. MCA/MFA
MCA=1.25 x FLA
MFA = 1.1 x MCA, MFA
˺
4 x FLA
(If MFA is smaller than minimum standard value, Use minimum standard value in region for selecting circuit breaker.)
3. Next lower standard fuse rating. Minimum 15A.
4. Select wire size based on the MCA.
5. MFA is used to select the circuit breaker and ground fault circuit interrupter, and all installation site must require attachment of an earth leakage breaker.
[circuit breaker type is ELCB(Earth Leakage Circuit Breaker)].
Model
PRHR023
PRHR033
PRHR043
Max. Connectable No. of Indoor Units
16
24
32
Max. Connectable No. of Indoor Units of a branch
8
8
8
Nominal Input
Cooling(W)
39.8
39.8
39.8
Heating(W)
37.2
37.2
37.2
Net. Weight
kg
16.0
17.8
19.3
lbs
35.3
39.2
42.5
Dimensions
(WxHxD)
mm
786 x 218 x 657
Inch
30-15/16 × 8-19/32 × 25-7/8
Casing
Galvanized steel plate
Connecting Pipes
Indoor side
Liquid Pipe [mm/inch]
Ø9.52[3/8] ~ Ø6.35[1/4]
Gas Pipe [mm/inch]
Ø15.88[5/8] ~ Ø12.7[1/2]
Outdoor side
Liquid [mm/inch]
Ø9.52[3/8]
Ø12.7[1/2]
Ø15.88[5/8]
Low Pressure [mm/inch]
Ø22.2[7/8]
Ø28.58[1-1/8]
Ø28.58[1-1/8]
High Pressure [mm/inch]
Ø19.05[3/4]
Ø22.2[7/8]
Ø22.2[7/8]
Sound Absorbing Insulation Material
Polyethylene Foam
Current
Minimum circuit Amps(MCA)
0.17
Power Supply
1Ø, 220-240V, 50Hz / 1Ø, 220V, 60Hz
Содержание ARUM080LTE5
Страница 1: ...Heat Recovery Heat Pump R410A 50Hz 60Hz 0CVV0 01E Replaces 0CVV0 01D P No MFL67474071 ...
Страница 85: ...78 Multi V 5 Outdoor Units 4 Wiring Diagrams 4 1 8 10 12 HP UXA 1 Comp ...
Страница 86: ...4 Wiring Diagrams 79 Multi V 5 Outdoor Units 4 2 14 16 HP UXB 1 Comp ...
Страница 87: ...Multi V 5 4 Wiring Diagrams 80 Outdoor Units 4 3 18 20 22 24 26HP UXB 2 Comp ...
Страница 703: ...5 Multi V 5 Heat Recovery HR Unit 3 Dimensions PRHR023 PRHR033 PRHR043 481 176 125 311 150 150 486 500 218 40 55 19 ...
Страница 704: ...Multi V 5 Heat Recovery 3 Dimensions 6 HR Unit PRHR063 PRHR083 809 218 55 40 19 793 160 160 481 176 311 125 ...
Страница 766: ...Special Guide Multi V 5 1 Cautions for Refrigerant Leaks 2 Guide for installing at seaside ...