Multi V 5
7. Refrigerant piping system
16
Installation of Outdoor Units
■
Refrigerant pipe diameter from branch to branch (B,C)
■
(**) Conditional Application
If the below conditions are satisfied, limit of longest pipe length after 1st branch(
l
) could be extended by 40m
(131ft)
→
90m(295ft).
1.
Pipe diameter Size Up
Pipe diameter(only Liquid/low pressure gas pipes) between 1st branch and last branch(HR unit) is increased by
one step. If the pipe diameter of B, C3 is same as A, it is not necessary.
: Ø 6.35
→
Ø 9.52
→
Ø 12.7
→
Ø 15.88
→
Ø 19.05
→
Ø 22.2
→
...
If available on site, select pipe size from the pipe diameter table according to capacity.
Otherwise it doesn’t need to be increased.
2.
Correction for calculating the total pipe length
When calculating total pipe length, pipe B,C,D length should be calculated twice.
: A + B x 2 + C3 x 2 + D x 2 + C1 + C2 + a + b + c + d + e + f + g + i + j + k + l + m + n
≤
1,000m (3,281ft)
3.
Indoor unit pipe length
Length of pipe from each indoor unit to the closest HR unit (a, b, c, d, e, f, g, i, j, k, l, m, n)
≤
40m (131ft).
4.
Difference in length between outdoor unit and the farthest or closest indoor unit
[Length of pipe from outdoor unit to the farthest indoor unit 12 (B + C3 + D + k)]
- [Length of pipe from outdoor unit to the closest indoor unit 1 (C1 + a)]
≤
40m (131ft)
Downward indoorunit total
capacity[kW(Btu/h)]
Liquid pipe[mm(inch)]
Gas pipe [mm(inch)]
Low pressure
High pressure
≤
5.6(19,100)
Ø6.35(1/4)
Ø12.7(1/2)
Ø9.52(3/8)
< 16.0 (54,600)
Ø9.52(3/8)
Ø15.88(5/8)
Ø12.7(1/2)
< 22.4 (76,400)
Ø9.52(3/8)
Ø19.05(3/4)
Ø15.88(5/8)
< 33.6(114,700)
Ø9.52(3/8)
Ø22.2(7/8)
Ø19.05(3/4)
< 50.4(172,000)
Ø12.7(1/2)
Ø28.58(1-1/8)
Ø22.2(7/8)
< 67.2(229,300)
Ø15.88(5/8)
Ø28.58(1-1/8)
Ø22.2(7/8)
< 72.8(248,400)
Ø15.88(5/8)
Ø34.9(1-3/8)
Ø28.58(1-1/8)
< 100.8(344,000)
Ø19.05(3/4)
Ø34.9(1-3/8)
Ø28.58(1-1/8)
< 173.6(592,500)
Ø19.05(3/4)
Ø41.3(1-5/8)
Ø34.9(1-3/8)
< 184.8(630,700)
Ø22.2(7/8)
Ø41.3(1-5/8)
Ø34.9(1-3/8)
≤
291.2(993,600)
Ø22.2(7/8)
Ø53.98(2-1/8)
Ø41.3(1-5/8)
Содержание ARUM080LTE5
Страница 1: ...Heat Recovery Heat Pump R410A 50Hz 60Hz 0CVV0 01E Replaces 0CVV0 01D P No MFL67474071 ...
Страница 85: ...78 Multi V 5 Outdoor Units 4 Wiring Diagrams 4 1 8 10 12 HP UXA 1 Comp ...
Страница 86: ...4 Wiring Diagrams 79 Multi V 5 Outdoor Units 4 2 14 16 HP UXB 1 Comp ...
Страница 87: ...Multi V 5 4 Wiring Diagrams 80 Outdoor Units 4 3 18 20 22 24 26HP UXB 2 Comp ...
Страница 703: ...5 Multi V 5 Heat Recovery HR Unit 3 Dimensions PRHR023 PRHR033 PRHR043 481 176 125 311 150 150 486 500 218 40 55 19 ...
Страница 704: ...Multi V 5 Heat Recovery 3 Dimensions 6 HR Unit PRHR063 PRHR083 809 218 55 40 19 793 160 160 481 176 311 125 ...
Страница 766: ...Special Guide Multi V 5 1 Cautions for Refrigerant Leaks 2 Guide for installing at seaside ...