11
Multi V 5
Installation of Outdoor Units
6. Refrigerant piping Installation
6.1 Precautions on Pipe connection / Valve operation
WARNING
• Always careful not to leak the refrigerant during welding.
• The refrigerant generates poisonous gas harmful to human body if combusted.
• Do not perform welding in a closed space.
• Be sure to close the cap of the service port to prevent gas leakage after the work.
CAUTION
Please block the pipe knock outs of the front and side panels after installing the pipes.
(Animals or foreign objects may be brought in to damage the cables.)
Pipe connection is done by connecting from the end of the pipe to
the branching pipes, and the refrigerant pipe coming out of the
outdoor unit is divided at the end to connect to each indoor unit.
Flare connection for the indoor unit, and welding connection for the
outdoor pipe and the branching parts.
• Use hexagonal wrench to open/close the valve.
• In case of installing as heat pump system, be sure to maintain to
close no use pipe like below picture.
[Heat Pump]
[Heat Recovery]
Liquid Pipe
No Use(Keep Closed)
Gas Pipe
Service Port
Liquid Pipe
Low Pressure Gas Pipe
High Pressure Gas Pipe
Service Port
Содержание ARUM080LTE5
Страница 1: ...Heat Recovery Heat Pump R410A 50Hz 60Hz 0CVV0 01E Replaces 0CVV0 01D P No MFL67474071 ...
Страница 85: ...78 Multi V 5 Outdoor Units 4 Wiring Diagrams 4 1 8 10 12 HP UXA 1 Comp ...
Страница 86: ...4 Wiring Diagrams 79 Multi V 5 Outdoor Units 4 2 14 16 HP UXB 1 Comp ...
Страница 87: ...Multi V 5 4 Wiring Diagrams 80 Outdoor Units 4 3 18 20 22 24 26HP UXB 2 Comp ...
Страница 703: ...5 Multi V 5 Heat Recovery HR Unit 3 Dimensions PRHR023 PRHR033 PRHR043 481 176 125 311 150 150 486 500 218 40 55 19 ...
Страница 704: ...Multi V 5 Heat Recovery 3 Dimensions 6 HR Unit PRHR063 PRHR083 809 218 55 40 19 793 160 160 481 176 311 125 ...
Страница 766: ...Special Guide Multi V 5 1 Cautions for Refrigerant Leaks 2 Guide for installing at seaside ...