5. Field Wiring
86
Outdoor Units
WARNING
•
Indoor Unit ground Lines are required for preventing electrical shock accident during current leakage,
Communication disorder by noise effect and motor current leakage (without connection to pipe).
•
Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from
the power supply.
•
Install the main switch that can interrupt all the power sources in an integrated manner because this
system consists of the equipment utilizing the multiple power sources.
•
If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on
and off while the product is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
Between Indoor and Master Outdoor unit
The GND terminal at the main PCB is a ‘-’ terminal for dry contact. It is not the point to make ground connection.
• Make sure that terminal number of master and slave outdoor units are matched.(A-A,B-B)
̰
Example Connection of Communication Cable
• Connection of communication cable must be installed
like below figure between indoor unit to outdoor unit.
• Abnormal operation can be caused by communication
defect, when connection of communication cable
isinstalled like below figure.
BUS Type
STAR Type
3
4
3
4
3
4
Slave1
Outdoor Unit
Master
Outdoor unit
Slave2
Outdoor Unit
Master
Outdoor Unit
SODU.B SODU.A
IDU.B IDU.A
CEN.B
CEN.A
DRY1
DRY2
GND
12V
SODU.B SODU.A
IDU.B IDU.A
CEN.B
CEN.A
DRY1
DRY2
GND
12V
SODU.B SODU.A
IDU.B IDU.A
CEN.B
CEN.A
DRY1
DRY2
GND
12V
SODU.B SODU.A
IDU.B IDU.A
CEN.B
CEN.A
DRY1
DRY2
GND
12V
Содержание ARUM080LTE5
Страница 1: ...Heat Recovery Heat Pump R410A 50Hz 60Hz 0CVV0 01E Replaces 0CVV0 01D P No MFL67474071 ...
Страница 85: ...78 Multi V 5 Outdoor Units 4 Wiring Diagrams 4 1 8 10 12 HP UXA 1 Comp ...
Страница 86: ...4 Wiring Diagrams 79 Multi V 5 Outdoor Units 4 2 14 16 HP UXB 1 Comp ...
Страница 87: ...Multi V 5 4 Wiring Diagrams 80 Outdoor Units 4 3 18 20 22 24 26HP UXB 2 Comp ...
Страница 703: ...5 Multi V 5 Heat Recovery HR Unit 3 Dimensions PRHR023 PRHR033 PRHR043 481 176 125 311 150 150 486 500 218 40 55 19 ...
Страница 704: ...Multi V 5 Heat Recovery 3 Dimensions 6 HR Unit PRHR063 PRHR083 809 218 55 40 19 793 160 160 481 176 311 125 ...
Страница 766: ...Special Guide Multi V 5 1 Cautions for Refrigerant Leaks 2 Guide for installing at seaside ...