8. Capacity Correction Factor
672
Multi V 5
Outdoor Units
Note
1. These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load under
standard conditions.(Moreover, under partial load conditions there is only a minor deviation from the rate of
change in capacity shown in the above figures.)
2. With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant
control when heating is carried out.
3. If heat insulation of piping is insufficient, heat loss will become larger and capacity will decrease.
4. Method of calculating cooling / heating capacity : maximum cooling / heating capacity of outside units = cooling
/ heating capacity of outside units obtained from capacity table X capacity correction factor due to piping length
to the farthest indoor unit
5. Equivalent piping length for Y Branch and other pipes can be calculated with following table.
6. When the any one (or both ) of below conditions are satisfied, the diameter of main pipe must be increased.
• The equivalent length between outdoor unit and the farthest indoor unit is 90m or more (Liquid or Gas pipes
are increased in accordance with below table)
• The level difference (Outdoor unit
˩
Indoor unit) is 50m or more (Only liquid pipe is increased)
Refer to the table (Refrigerant pipe diameter from outdoor unit to first branch.) in the 'installation of outdoor units'
part.
7. Read cooling / heating capacity rate of change in the above figures based on the following equivalent length. :
overall equivalent length = (equivalent length of main pipe) X correction (equivalent length after first
branching)
•
8, 10, 12, 14, 16, 18, 20, 22, 24, 26, 28, 30, 32, 34HP
•
36, 38, 40, 42, 44, 46, 48, 50, 52, 54, 56, 58, 60HP
•
62, 64, 66, 68, 70, 72, 74, 76, 78, 80, 82, 84, 86, 88, 90, 92, 94, 96HP
mm
(inch)
Ø6.35
(1/4)
Ø9.52
(3/8)
Ø12.7
(1/2)
Ø15.88
(5/8)
Ø19.05
(3/4)
Ø22.2
(7/8)
Ø25.4
(1)
Ø28.58
(1-1/8)
Ø31.8
(1-1/4)
Ø34.9
(1-3/8)
Ø38.1
(1-1/2)
Ø41.3
(1-5/8)
Ø44.5
(1-3/4)
Ø53.98
(2-1/8)
Elbow (m)
0.16
0.18
0.2
0.25
0.35
0.4
0.45
0.5
0.55
0.6
0.65
0.7
0.75
0.85
Y Branch (m)
0.5
Header (m)
1
HR Unit (m)
2.5
Rate of change
(object piping)
Correction factor
standard size
size increase
Cooling(Gas pipe)
1
0.5
Heating(Liquid pipe)
1
0.2
Rate of change
(object piping)
Correction factor
standard size
size increase
Cooling(Gas pipe)
1
0.5
Heating(Liquid pipe)
1
0.4
Rate of change
(object piping)
Correction factor
standard size
size increase
Cooling(Gas pipe)
1
-
Heating(Liquid pipe)
1
0.4
Содержание ARUM080LTE5
Страница 1: ...Heat Recovery Heat Pump R410A 50Hz 60Hz 0CVV0 01E Replaces 0CVV0 01D P No MFL67474071 ...
Страница 85: ...78 Multi V 5 Outdoor Units 4 Wiring Diagrams 4 1 8 10 12 HP UXA 1 Comp ...
Страница 86: ...4 Wiring Diagrams 79 Multi V 5 Outdoor Units 4 2 14 16 HP UXB 1 Comp ...
Страница 87: ...Multi V 5 4 Wiring Diagrams 80 Outdoor Units 4 3 18 20 22 24 26HP UXB 2 Comp ...
Страница 703: ...5 Multi V 5 Heat Recovery HR Unit 3 Dimensions PRHR023 PRHR033 PRHR043 481 176 125 311 150 150 486 500 218 40 55 19 ...
Страница 704: ...Multi V 5 Heat Recovery 3 Dimensions 6 HR Unit PRHR063 PRHR083 809 218 55 40 19 793 160 160 481 176 311 125 ...
Страница 766: ...Special Guide Multi V 5 1 Cautions for Refrigerant Leaks 2 Guide for installing at seaside ...