Chapter 4. CPU module
4 - 31
4.5.3 Remote function
The CPU module can be controlled by external operations (from GMWIN and computer link module, etc.). For
remote operation, set the mode setting switch of CPU module to remote position.
1) Remote RUN/STOP
(1) The remote RUN/STOP permits external operations to RUN/STOP the CPU module under the condition
that the mode setting switch of CPU module is in the remote position.
(2) This function is convenient when the CPU module is located on the place where it is difficult to control the
CPU module or the user want to control the CPU module in the control panel from outside.
2) Remote PAUSE
(1) The remote PAUSE permits external operations to execute PAUSE operations under the condition that the
mode setting switch of CPU module is in the remote position. The PAUSE operations stop the CPU module
operation processing while maintaining the On/Off state of the output module.
(2) This function is convenient when the user wants to maintain the ON state of the output module under the
condition the CPU module has been stopped.
3) Remote DEBUG
(1) This function permits external operations to execute DEBUG operations under the condition that the mode
setting switch of CPU module is in the remote position. The DEBUG operations execute programs complying
with the specified operation conditions.
(2) This function is convenient when program execution or contents of any data are checked for debugging of
the program.
4) Remote reset
(1) This function permits remote operations to reset the CPU module, which locates in the place where direct
operations cannot be applied, when an error has occurred.
REMARK
1) For remote function operations, refer to the GMWIN User’s Manual Chapter 7. On-line.
Содержание GLOFA GM6 Series
Страница 1: ...U s e r s M a n u a l LG Programmable Logic Controller GLOFA GM6 Series L G Industrial Systems ...
Страница 2: ... CONTENTS ...
Страница 178: ...Chapter 15 The PID functions 15 24 Example program of 15 4 3 1 ...
Страница 179: ...Chapter 15 The PID functions 15 25 Example program of 15 4 3 2 continue to next page ...
Страница 180: ...Chapter 15 The PID functions 15 26 Example program of 15 4 3 2 continued ...
Страница 209: ...Appendix 4 Outer Dimensions APP4 3 ...