Chapter 7. INPUT AND OUTPUT MODULES
7- 9
7.3 Digital Output Module Specifications
7.3.1. 8-point relay output module
Relay Output Module
Models
Specifications
G6Q-RY1A
Number of output points
8 points
Insulation method
Photo coupler
Rated load voltage & current
24 VDC 2A(resistance)/point, 5 A/ COM
220 VAC 2A(COS
Ψ
= `1)/point, 5A/COM
Minimum load voltage/current
5 VDC / 1 mA
Maximum load voltage/current
250 VAC, 110 VDC
Maximum switching frequency
1200 times per hour
Surge absorber
None
Mechanical
20 million times or more
Rated load voltage/current 100000 times or more
200 VAC 1.5 A, 240 VAC 1 A (COS
Ψ
= 0.7) : 100000 times or more
200 VAC 1 A, 240 VAC 0.5 A (COS
Ψ
= 0.35) : 100000 times or more
Service life
Electrical
24 VAC 1.5 A, 100 VDC 0.1 A (L/R= 7 ms) : 100000 times or more
Off
→
On
10 ms or less
Response time
On
→
Off
12 ms or less
Common terminal arrangement
1 points/COM
Internal current consumption
250mA
Operation indicator
LED turns on at ON state of output
External connections
18-point terminal block connector (M3
×
6 screws)
Weight
0.19 kg
AC110/220V
00
Internal
Circuit
1
DC5V
Terminal
Block No.
R
R
DC5V
Coil
L
16
15
L
Relay
G6Q-RY1A
L
01
02
03
04
05
07
06
COM
L
L
00
2
NC
17
18
07
L
L
L
L
L
L
COM
COM
COM
COM
COM
COM
COM
NC
NC
Содержание GLOFA GM6 Series
Страница 1: ...U s e r s M a n u a l LG Programmable Logic Controller GLOFA GM6 Series L G Industrial Systems ...
Страница 2: ... CONTENTS ...
Страница 178: ...Chapter 15 The PID functions 15 24 Example program of 15 4 3 1 ...
Страница 179: ...Chapter 15 The PID functions 15 25 Example program of 15 4 3 2 continue to next page ...
Страница 180: ...Chapter 15 The PID functions 15 26 Example program of 15 4 3 2 continued ...
Страница 209: ...Appendix 4 Outer Dimensions APP4 3 ...