Chapter 7. INPUT AND OUTPUT MODULES
7- 15
7.3.7 8-point triac output module
Triac Output Module
Models
Specifications
G6Q-SS1A
Number of output points
8 points
Insulation method
Photo coupler
Rated load voltage
100 to 240 VAC (50 to 60 Hz)
Minimum load voltage
264 VAC
Maximum load current
1 A / point, 4 A / 1 COM
Minimum load current
20 mA
Off leakage current
2.5 mA (220 VAC, 60 Hz)
Maximum inrush current
40 A, 10 ms or less
Maximum voltage drop at ON circuit
1.5 VAC or less (2 A)
Surge absorber
Varistor (387 to 473 V), C.R absorber
Off
→
On
1ms or less
Response time
On
→
Off
1ms + 0.5 cycle or less
Common terminal arrangement
8 points/COM
Internal current consumption
210 mA
Operation indicator
LED turns on at ON state of output
External connections
9-point terminal block connector (M3
×
6 screws)
Weight
0.16 kg
Wiring Diagram
00
L
01
L
02
L
03
L
04
L
05
L
06
L
07
L
100 ~ 240 VAC