Chapter 16. Built-in high speed counter of GM6-CPUC
16-7
C H S C _ R D
C H S C _ R D
GM1
GM2
GM3
GM4
GM5
GM6
λ
FUNCTION BLOCK
Description
REQ
STAT
DONE
BOOL
CHSC_RD
BOOL
USINT
CY
CNT
UDINT
BOOL
I n p u t
REQ : Request signal for F/B execution
O u t p u t
DONE : Turns on after the F/B is executed with no
error.
STAT : Indicates the operation status of F/B
CNT : The current value of HSC
(0 ~ 16,777,215)
CY : Carry flag (0 : OFF, 1 : ON)
Read the current value and operation
status of HSC