Commissioning and configuration
Leuze electronic
BCL 504
i
153
TNT 35/7-24V
10.12 Switching inputs/ outputs SWIO 1..4
These modules define the mode of operation of the 4 digital switching inputs and outputs (I/
Os). They are separated into individual modules for configuring the individual I/Os and a
shared module for signalling the status and controlling.
10.12.1 Parameters for operating as an output
Start-up delay
With this setting, the output pulse can be delayed by the specified time (in ms).
Switch-on time
Defines the switch-on time period for the switching input. Any activated switch-off function
then no longer has any function.
A value of 0 causes the output to be set statically; this means that the selected input func-
tion(s) activate the output, and the selected switch-off function(s) deactivate it again.
Figure 10.2: Example 1: Start-up delay > 0 and switch-on time = 0
Figure 10.3: Example 2: Start-up delay > 0 and switch-on time > 0
In example 2, the activation duration of the output is only dependent on the selected switch-
on time; the switch-off signal has no effect.
Switch-on signal
Switch-off signal
Output
Start-up delay
Switch-on signal
Switch-off signal
Output
Switch-on time
Start-up delay