Commissioning and configuration
Leuze electronic
BCL 504
i
173
TNT 35/7-24V
Parameter length
8 byte
Input data
None
Output data
None
Barcode com-
parison mode
This parameter
specifies which
decoded barcodes
are to be used for
the reference bar-
code comparison.
6
UNSIGNED8
0: Only the first barcode is used
for the comparison.
1: Only the second barcode is
used for the comparison.
2: All barcodes are used for the
comparison. All comparisons
must be successful.
3: All barcodes are used for the
comparison. One compari-
son must be successful.
3
-
Reference code
completeness
comparison
If this parameter is
set, the basic condi-
tion for a positive ref-
erence code
comparison is that all
mandatory bar-
codes that are to be
read within a reading
gate were actually
read. If this condi-
tion is not satisfied,
no positive refer-
ence code compari-
son is achieved.
7.0
Bit
0: Completeness comparison
switched off.
1: Completeness comparison
switched on.
0
-
Parameter
Description
Addr.
Data type
Value range
Default
Unit
Table 10.56:
Parameters for module 82 – Reference code comparison